P28 - - - a Echo-loss handling
FACTORY DEFAULT: 0
a
E
CHO
-
LOSS ERROR
INDICATION
R
EMARK
0
Delayed
During short periods of echo-loss, both Eview and the analogue output will hold last value. The current
output holds last value for twice as long as set in
P20
before going to the
"
Error Indication Mode
"
set in
P12
.
1
None
During an echo-loss the displayed value on the EView and the analogue output value will hold last value.
2
Advance to full
When echo-loss occurs during filling, the displayed value on the EView and the analogue output value
shifts towards the
"
full
"
tank/silo state with the level elevation rate (filling speed) set in
P26
3
Immediate
In case of an echo-loss, ‘no Echo’ will appear in EView and the outputs will change according to the
"
Error Indication Mode
"
set in
P12
.
4
No echo-loss indication
in case of empty
tank/silo
Echo-loss may occur in completely empty tanks with a spherical bottom due to deflection of the ultrasonic
beam, or in case of silos with an open outlet. If the echo is lost when the tank/silo is completely empty, the
indication will correspond to empty tank, in all other cases echo-loss indication will function according to
the “Delayed”.