background image

ISSUE:

02

No:

DATE:

PAGE:

1

of

9

OCTOBER 2006

NISM/NAMAS3/02

NAM-AS3 LOOP POWERED

  INPUT MODULE

INSTALLATION & TECHNICAL

MANUAL

INTRODUCTION

DESCRIPTION

The NAM-AS3 forms part of the Nittan (UK)'s
SENSORTEC-ANALOGUE range of Analogue
Addressable Devices.

This module is designed to perform a loop powered,
addressable input module  function from the detection
signalling loop of an analogue-addressable fire detec-
tion system.

The NAM-AS3 may be used for a variety of purposes
such as monitoring a 'relay contact input' or monitor the
operation of a 'sprinkler flow monitoring switch'.

OPERATION

The fire alarm control equipment must be capable of
communicating with the NAM-AS3 input module.  If in
doubt, check with panel manufacturer.

The NAM-AS3 is a loop powered, two-wire signalling de-
vice, it is connected onto the detection signalling loop's
SIG+ and -S wires, exactly as any other 'AS' sensor or
device.

FEATURES

* Monitoring a relay contact input.

* Monitoring the operation of a sprinkler flow switch.

NAM-AS3 Input Module is made up as
follows:-

1 x Metal enclosure c/w 20mm knockouts
1 x NAM-AS3 PCB c/w internal plastic PCB enclosure
with hinged lid.
1 x Earth point (on lid)
1 x Earth point (inside of enclosure)
1 x 200mm Earth Strap
1 x Label inside lid for product identification and
device address identification.

INPUT MODULE NAM-AS3

SENSORTEC-ANALOGUE FAMILY:-

SENSORS:-
ST-I-AS
 - Analogue Ionisation Smoke Sensor
ST-P-AS - Analogue Photoelectric Smoke Sensor
ST-H-AS - Analogue Heat Sensor
STB-4 - Standard Base for above sensors

DEVICES:-
ST-NCP-AS
 - Addressable Call Point
BACK BOX - Back Box for ST-NCP-AS
MCM-AS4 - Zone Monitor/Control Unit
SCM-AS4- Addressable Sounder Control Module
NAM-AS3 - Addressable Input Module
OCM-AS3 - Output Control Module
SCI-5 - Base mounted Short Circuit Isolator
SCI-6 - Plate mounted Short Circuit Isolator
1-Gang Box - Single gang box  for SCI-6

ADDRESSABLE SOUNDERS:-
VCT-03-AS-NB 
 - Addressable Wall Sounder
c/w Vector Plate/Cap (R = Red, W = White Plate/Cap).
VCT-03-CP(W) - Spare Vector Plate/Cap (White)
VCT-03-CP(R) - Spare Vector Plate/Cap (Red)
VCT-03-NT-AS - Addressable Sounder c/w STB-4 Base
pre-wired to the sounder.
VPR-SA2-NTAS - Addressable Sounder, IP65 rated,
wall mounted.

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание NAM-AS3

Страница 1: ...le is made up as follows 1 x Metal enclosure c w 20mm knockouts 1 x NAM AS3 PCB c w internal plastic PCB enclosure with hinged lid 1 x Earth point on lid 1 x Earth point inside of enclosure 1 x 200mm...

Страница 2: ...kout holes for cable gland entry to the main enclosure of NAM AS3 b Using the template on page 5 of this manual mark and drill the main enclosure screw positions in the wall c Position the NAM AS3 enc...

Страница 3: ...D REMOVED SIDE VIEW 1 SIDE VIEW 2 20 0mm KNOCKOUTS EARTHSTUD 2 X LOWER PCB ENCLOSURE FIXINGSCREWS TOPPCB ENCLOSURE FIXINGSCREW PCB ENCLOSURE 20 0mm KNOCKOUTS PCB CABLETERMINALS 1 3 87 2 On 4 65 LED C...

Страница 4: ...of 9 OCTOBER2006 NISM NAMAS3 02 NAM AS3 LOOP POWERED INPUT MODULE INSTALLATION TECHNICAL MANUAL ENCLOSURE OUTER DIMENSIONS 163mm 44mm 204mm NOT TO SCALE 130mm 185mm 20 0mm www acornfiresecurity com ww...

Страница 5: ...9 OCTOBER2006 NISM NAMAS3 02 NAM AS3 LOOP POWERED INPUT MODULE INSTALLATION TECHNICAL MANUAL ENCLOSURE DIMENSIONS INTERNAL MOUNTING HOLES NOT TO SCALE 20 0mm 110mm 142mm 4 0mm www acornfiresecurity co...

Страница 6: ...ISSUE 02 No DATE PAGE 6 of 9 OCTOBER2006 NISM NAMAS3 02 NAM AS3 LOOP POWERED INPUT MODULE INSTALLATION TECHNICAL MANUAL ENCLOSURE MOUNTING TEMPLATE www acornfiresecurity com www acornfiresecurity com...

Страница 7: ...N TECHNICAL MANUAL ENCLOSURE INTERNAL ASSEMBLY DIMENSIONS 163mm NOT TO SCALE 20 0mm 22mm 22mm 30mm 30mm 54mm 48mm 160mm 1 3 87 2 On 4 65 LED C L LEDINDICATIONS DIL Address SettingSwitch COMMS TRIGGERE...

Страница 8: ...28 ADDRESS SETTING CONNECTIONS TO NAM AS3 PCB CONNECTION DETAILS PCB AND ADDRESS SETTING N OFIRE CONTACT NAM AS3 C S L SIG LOOP WIRING Screen LINK PLK FIRE LED ON FIRE LED OFF IN OUT OUT IN 1 3 87 2 O...

Страница 9: ...0 A Quiescent c w conventional detector zone From loop 24v 4mA Max PowerSupplyRequirements Loop Powered No external PSU required LED Indications On Board LED Indication a Red COMMS LED Pulses when pol...

Страница 10: ...comes SENSORTEC Document No NISM NAMAS3 02 Date OCTOBER2006 Pages 10 inc cover www acornfiresecurity com www acornfiresecurity com...

Отзывы: