Technical Manual: EVC-H - 000014 (Changes are subject to DCRN)
9
• Ref No: NISM/EVC-H/05 • Date: 23.01.19 • Issue: 5
• evolution • EV C-H • heat detector instruction manual
Typical Application Temperature:
EVC-H-A2S 25 ºC
EVC-H-CS 55 ºC
Maximum Application Temperature:
EVC-H-A2S 50 ºC
EVC-H-CS 80 ºC
Min. and Max.
EVC-H-A2S 54 ºC / 70 ºC
Static Response Temperature:
EVC-H-CS 84 ºC / 100 ºC
Min. Ambient Temperature:
-10 ºC
IP Rating:
40
Section 9 - EMC
Installation
The installation shall be in accordance with the regulations
either of the approval body for an approved system,
or otherwise, to the national code of practice/ regulations
for the installation of the fire alarm system, e.g. BS 5839 part 1.
Electromagnetic Compatibility (EMC)
On a site where there is an unusually high level of potential
electrical interference, e.g. where heavy currents are being
switched or where high levels of R.F. are prevalent, then care
must be taken in the type and routing of cables. Particular care
should be given to the separation of zone wiring from the
cable carrying the interference.
Section 10 - DIMENSIONS
15mm
42.5mm
105mm
Fig. 5