• evolution • EV C-H • heat detector instruction manual

Typical Application Temperature: 

EVC-H-A2S 25 ºC

     

EVC-H-CS 55 ºC

Maximum Application Temperature: 

EVC-H-A2S 50 ºC

     

EVC-H-CS 80 ºC

Min. and Max.  

EVC-H-A2S 54 ºC / 70 ºC

Static Response Temperature: 

EVC-H-CS 84 ºC / 100 ºC

Min. Ambient Temperature: 

-10 ºC 

IP Rating:  

40

Section 9 - EMC

Installation

The installation shall be in accordance with the regulations 
either of the approval body for an approved system, 
or otherwise, to the national code of practice/ regulations 
for the installation of the fire alarm system, e.g. BS 5839 part 1.

Electromagnetic Compatibility (EMC)

On a site where there is an unusually high level of potential 
electrical interference, e.g. where heavy currents are being 
switched or where high levels of R.F. are prevalent, then care 
must be taken in the type and routing of cables. Particular care
 should be given to the separation of zone wiring from the 
cable carrying the interference.

Section 10 - DIMENSIONS

15mm  

42.5mm  

105mm 

Fig. 5

Содержание Evolution EVC-H Series

Страница 1: ...1483 769555 Fax 44 0 1483 756686 Web Site www nittan co uk E mail sales nittan co uk Ref No NISM EVC H 05 Date 23 01 19 Issue 5 evolution EV C H heat detector instruction manual EVC H HEAT DETECTOR i...

Страница 2: ...e Ltd called evolution The EVC H is an elegantly designed low profile detector which is aesthetically pleasing thus enabling it to blend unobtrusively into modern working environments The EVC H is com...

Страница 3: ...Page 9 Section 11 Disposal Page 10 Section 12 ROHS Compliance Page 10 Statement Section 1 INTRODUCTION The EVC H is an attractively styled fast response low profile heat detector It has been designed...

Страница 4: ...indicator Section 4 BASE MODELS A variety of bases are available for use with the EVC H detectors It is important to use the correct base for each application The available Base models are i STB 4 UB...

Страница 5: ...DUST COVER MUST BE REMOVED FROM THE SENSOR IN ORDER FOR THE SENSOR TO FUNCTION CORRECTLY Section 6 CONNECTIONS Connections are made to the detector base The connections used depend on the type of base...

Страница 6: ...uld be conducted with the following frequency One month after installation Routine Inspection and every 3 months thereafter Every 6 months Operational Test Every 12 months Functional Test and Cleaning...

Страница 7: ...at from a warm air gun designed for heat detector testing e g No Climb Solo heat sensor tester Check that the detector gives an alarm condition within 10 20 seconds depending upon the detector grade a...

Страница 8: ...m the apertures on the plastic case iv Ensure that no debris is left on or around the thermistor once cleaning is complete v If the unit needs further cleaning or is damaged or corroded please return...

Страница 9: ...ion shall be in accordance with the regulations either of the approval body for an approved system or otherwise to the national code of practice regulations for the installation of the fire alarm syst...

Страница 10: ...g please contact your local city office or your household waste disposal service Section 12 ROHS COMPLIANCE STATEMENT RoHS compliant and lead free This product complies with the RoHS Restriction of Ha...

Отзывы: