Instruction  Manual

           

   

                   

 

EVA-ZMU-SCI    Zone Module

                                               

 

Before Installation 

Please read these instructions carefully and keep for future reference.   

The  information  in  this  document  is  subject  to change  without notice. 

For updates please refer to our website. 

 
 
 
 
 
 
 
 

Note

  : 

Follow  the  requirements  for  the  installation  of  the  product  in 

accordance with the Specifications. Otherwise it may cause malfunction.

 

Note 

: 

Do not install the product in any location where oil, dust, iron 

powder, chemicals, or hydrogen sulphide may occur or affect the product. 

It may cause malfunction.

   

 

This package contains the following items: 

Main  unit

  ………………………………………………………………

Outer  cover  EVA

…………………………………………………………

Instruction  Manual

  ……………………………………………………

Tapping  screw

  …………………………………………………………

Pan  head  screw   

…………………………………………………………

EOL  Resistor(RE-10k)

………………………………………………………

 

General Description 

EVA-ZMU-SCI Zone Module with Short Circuit Isolator is intended for 

use  in  addressable  two  wire  systems,  which  can  be  connected  with 

2-wire conventional detectors. The module monitors and transmits the 

status  (normal,  open,  short,  or  alarm)  of  zone  with  the  detectors  to  a 

control panel. The initiating device circuit (IDC) can be wired on Class A 

or Class B.   

 

General Operation 

Normal standby condition: The module receives polling from the control 

panel at the regular interval. Polling LED (green) flashes. 

Alarm condition: When an external input is activated, Input LED (red) 

illuminates,  and  the  module  communicates  to  the  control  panel  the 

alarm status. 

Trouble condition: If an overcurrent occurs because SLC (Signaling Line 

Circuit)  is  shorted,  SCI  LED  (yellow)  illuminates,  and  the  module 

communicates  to  the  control  panel  the  short  status.  The  module  also 

communicates  to  the  control  panel  the  open/short  status  of  IDC, 

depending on the Subtype Setting described below.

 

 

SCI (Short Circuit Isolator) Function 

The  module  has  a  built-in  short  circuit  isolator.  SCI  circuit  prevents 

entire loop failure in the event of a short between L+ and L- on the loop. 

If  a  short  is  detected  between  L+  and  L-,  the  yellow LED  indicator  is 

illuminated.  The  line  between  Lin-  and  Lout-  is  disconnected 

automatically  to  isolate  the  short  circuit,  and  short  circuit  status  is 

communicated to the control panel. Upon removal of the short condition, 

the module will automatically connect between Lin- and Lout- to restore 

the entire loop to the normal operating status. 

Polling LED (GREEN)

Input LED (RED)

SCI LED (YELLOW)

Address Setting Port

 

Figure 1 

 

 

 

 

 

 

 

 

 

 

 

Figure 2 

NITTAN COMPANY, LIMITED

 

1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN 

 

http://www.nittan.com

 

Make  sure  to  turn  the  power  off  before  commencing  any  wiring  work. 

Otherwise it may cause electric shock or damage to equipment.

CAUTION

!

Do not disassemble, repair, or modify the products. It may cause a fire or 
electric shock.

CAUTION

!

Do not use the products outside the rated power supply voltage range 
specified in the Specifications. It may cause a fire or damage to 
equipment.