Classification
Beam type smoke detector (with test function)
Model
CKLD-KPT2
Allowable Distance
5m to 100m
Sensitivity
Distance
Sensitivity
5m to less than 15m
:
30
%
15m to less than 40m
:
40
%
40m to 100m
:
65
%
Rated Current/ Voltage
L-
C
:
Fire
Nominal Voltage
DC 24V
Monitoring current 760μA
Alarm current
65mA
K
-
C
:
Fault Nominal voltage
DC 24V
Alarm current
65mA
T
-
C
:
Test
Nominal voltage
DC 24V
Alarm current
100mA
Indicator
Transmitter
:
Power Indicator
(
red LED
)
Blinking in the monitoring state
Receiver:
Alarm indicator
(
red LED
)
Turning on in the alarm state
Other functions
Adjustment of receiving light intensity
Sensitivity compensation
Fault signal output
Terminal
Transmitter SL & SC
(
Transmission signal
)
×1 for each
Receiver
L & C
(
Fire signal
)
×2 for each
T
(
Test signal
)
×1
K
(
Fault signal
)
×2
KC
(
Fault signal
)
×1
SL & SC
(
Transmission signal
)
×1 for each
Compatible control panel
1PM2, 1PM3
Remote Station
LP04/LP05
Temperature & humidity
-10
℃
to 50
℃
Relative humidity
0
%
to 95
%(
no condensation
)
Note:
This product should not be installed in excessive humid
or condensing conditions.
Weight
Transmitter Approx. 500g
(
including the base
)
Receiver
Approx. 520g
(
including the base
)