Heating function:
Heating Mode:
When the water temperature is higher than or equal to the set value, the unit will not heat; When the measured
temperature below the set value- hysteresis, the heating element will start to heat the water.
Example: If it is set to heating mode, and temperature is set to 85 degrees, hysteresis is set to 5, when the measured
temperature is higher than or equal to 85 degrees, the heater is off. When the temperature drops below 80 degrees,
it will then begin to heat the water again.
Hysteresis Function:
Hysteresis setting limits the maximum interval between the heating and stopping, the minimum interval between the
opening and stopping is 1* F, the maximum is 30* F.
Hysteresis Settings:
Press SET key and hold more than 3 seconds to enter the menu display. With the Up or Down key adjust the screen to
where the “CP” is showing on the screen. Press the SET key to display the hysteresis set value, press Up or Down key
to adjust parameters, once you have the parameters where you want, press the set key again to save.
Bottle Temp vs.
Bottle Pressure
Degrees
(F)
Bottle
Pressure (Psi)
-30
167
-20
203
-10
240
0
283
10
335
20
387
32
460
40
520
50
590
60
675
70
760
80
865
85
950
97
1070
109
1150