             OV-G-V1: 220---290V                                OV-G-F1: 50.2-53Hz(60.2-64Hz)

             OV-G-V1-T: 0.1---9S                                  OV-G-F1-T: 0.1---9S

             OV-G-V2: 220---290V                                OV-G-F2: 50.2-53Hz(60.2-64Hz)

             OV-G-V2-T: 0.1---1S                                  OV-G-F2-T: 0.1---9S

             UN-G-V1: 90---210V                                  UN-G-F1: 47-49.5Hz(56-59.8Hz)

             UN-G-V1-T: 0.1---9S                                  UN-G-F1-T: 0.1---9S

             UN-G-V2: 90---210V                                  UN-G-F2: 47-49Hz(56-59.8Hz)

             UN-G-V2-T: 0.1---1S                                  UN-G-F2-T: 0.1---9S

.29.

.28.

Startup-T:10---600S
Restore-T:10---600S

Below is the setting range for “User-Def”. Using this function, the limits can be changed 

manually.

Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the highlighted 

item. Press the UP/DOWN keys again to change the setting. Press the ENTER key to save the 

setting. Press the ESC key to cancel changes and returns to the previous menu.

7.5.2 Grid ON/OFF

This function is used to start up or stop the power generation of Solis Three Phase 

Inverter (see Figure 7.17).

      Grid ON

        Grid OFF

Figure 7.17 Set Grid ON/OFF

Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key 

to save the setting. Press the ESC key to return to the previous menu. 

These two functions are applicable by maintenance personnel only, wrong 

operation will prevent the inverter from working properly.

7.5.4 New Password

This function is used to set the new password for menu “Advanced info.” and “Advanced 

information” (see Figure 7.18).

Figure 7.18 Set new password

YES=<ENT> NO=<ESC>

Password: 0000

Enter the right password before set new password. Press the DOWN key to move the cursor, 

Press the UP key to revise the value. Press the ENTER key to execute the setting. 

Press the ESC key to return to the previous menu. 

7.5.5 Power control

Active and reactive power can be set through power setting button.

There are 5 item for this sub menu:

1. Set output power     2. Set Reactive Power    3. Out_P With Restore     

4. Rea_P With Restore        5. Select PF Curve

This function is applicable by maintenance personnel only, wrong operation 

will prevent the inverter from reaching maximum power.

Selecting the “User-Def” menu will access to the following submenu (see Figure 7.16), 

Figure 7.16

       OV-G-V1: 260V

      OV-G-V1-T: 1S

NOTE:

The " User-Def" function can be only used by the service engineer and 
must be allowed by the local energy supplier.

7.5.3 Clear Energy

Clear Energy can reset the history yield of inverter

7.5.6 Calibrate Energy

Maintenance or replacement could clear or cause a different value of total energy. Use this 

function could allow user to revise the value of total energy to the same value as before. If 

the monitoring website is used the data will be synchronous with this setting automatically. 

(see Figure 7.19).

7. Operation

7. Operation

Содержание Solis 4G

Страница 1: ...Ltd Ningbo Ginlong Technologies Co Ltd No 57 Jintong Road Binhai Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem...

Страница 2: ...ts 3 3 Keypad 3 4 LCD 5 Installation 5 1 Select Location for the Inverter 5 2 Mounting the Inverter 5 3 Electrical Connections 7 Operation 6 Start Stop 6 1 Start the Inverter 6 2 Stop the Inverter 1 1...

Страница 3: ...ctor x2 User manual x1 Installation and Operation Manual Solis 4G Three Phase Inverter 5 10kW Ver 1 1 Ginlong Ningbo Technologies Co Ltd 1 Introduction 1 Introduction If anything is missing please con...

Страница 4: ...h the local and national electrical safety standards WARNING Please don t connect PV array positive or negative to ground it could cause serious damage to the inverter CAUTION The PV array Solar panel...

Страница 5: ...ys The keypad is used for Scrolling through the displayed options the UP and DOWN keys Access to modify the adjustable settings the ESC and ENTER keys The two line Liquid Crystal Display LCD is locate...

Страница 6: ...not blocked Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting Ginlong recommends inverter installed to avoid direct sunlight or...

Страница 7: ...ed hexagon head tapping screws HJ0108 10 50mm fished expandable tubular using the percussion drilling with the 10mm drill need to stay vertically on the wall And the drill hole must be vertically on t...

Страница 8: ...5 3 Electrical Connections Inverter designs quick connect terminal so top cover needn t open during electrical connection The sign meaning located the bottom of inverter as shown below in table 5 1 Al...

Страница 9: ...el all inverters should be connected to the same ground point to eliminate the possibility of a voltage potential existing between inverter grounds B insulation stripping length is 2mm 3mm longer than...

Страница 10: ...the Inverter The steps to assemble the DC connectors are listed as follows 1 Strip off the DC wire for about 7mm Disassemble the connector cap nut see Figure 5 13 3 Crimp the contact pin to the wire...

Страница 11: ...e is required to be used Please make sure the resistance of cable is lower than 1 50hm If the wire is longer than 20m preferred to 6mm cable Please fixed cable with PH1 cross screwdriver Each inverter...

Страница 12: ...ion 6 Start Stop 6 1 Start the Inverter To start up the Inverter it is important that the following steps are strictly followed 1 Switch the grid supply main Switch AC ON first 2 Switch the DC switch...

Страница 13: ...ing the ENTER key locks Figure 7 2 a or unlocks Figure 7 2 b the screen b a Figure 7 2 Locks and Unlocks the Screen of LCD 7 Operation 7 Operation Table 7 1 Information list V_DC1 350 8V I_DC1 5 1A V_...

Страница 14: ...ter menu Advanced Info and Advanced settings need password Select Advanced Info from the Main Menu The screen will require the password as below YES ENT NO ESC Password 0000 Figure 7 5 Enter password...

Страница 15: ...s history of changing settings Only for maintance personel 7 4 7 Communication Data The screen shows the internal data of the Inverter see Figure 7 14 which is for service technicians only 01 05 01 25...

Страница 16: ...is function is used to set the new password for menu Advanced info and Advanced information see Figure 7 18 Figure 7 18 Set new password YES ENT NO ESC Password 0000 Enter the right password before se...

Страница 17: ...international grid tied standards and safety and electromagnetic compatibility requirements Before delivering to the customer the inverter has been subjected to several tests to ensure its optimal ope...

Страница 18: ...BT current 12Power FAULT 12V power supply fault 1 Restart inverter or contact installer IG AD Grid current sampling fail DSP B FAULT Comm failure between main and slave DSP Table 9 1 Fault message and...

Страница 19: ...60 850 Start up voltage Volts 180 Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 N PE 400 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts M...

Страница 20: ...160 850 Start up voltage Volts 180 Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 N PE 400 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts...

Страница 21: ...ort circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 PE 208 220 240 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number...

Отзывы: