Electrical installation

Electrical connections

Safety

All work must be carried out by suitably qualified persons and in compliance with existing legislation
and regulations.

It is important that the power supply is disconnected when doing work to the electrical components of
the unit.

It is important to check that wires are not damaged or trapped during connection and use.

Connections overview

All electrical connections are located on front of the unit.

1. Connection of power supply cable for VPM
2. Cable grommets for various electrical connections and external sensors
3. Connection of HMI control panel

A. Connection of water after-heating element - supply flow

B. Connection of water after-heating element - return flow

A/B. Connection of electrical after-heating element

1

3

2

A

B

The illustration shown is for a left-facing version:

24

Содержание VPM 1000

Страница 1: ...INSTALLATION AND SERVICE INSTRUCTIONS CTS602I HMI BY NILAN VPM 600 2200 English Version 3 00 03 06 2020...

Страница 2: ...tion absorbers 13 Functional diagram VPM 600 2200 14 Accessories 15 CO2 sensor 15 Electrical after heating element 15 Filter monitoring Pressure transmitter 15 Humidity control 15 Handle with cylinder...

Страница 3: ...cessory 32 Ventilation installation Duct system 36 Legislation 36 Duct connections 36 Balancing 36 Important information 36 Performance curves for SEL value assessment 36 VPM 600 36 VPM 700 37 VPM 800...

Страница 4: ...r instance for installation inspection cleaning and filter replacement Pressure bearing equipment Exercise great caution when handling and disposing of heat pipes and refrigeration circuit elements Th...

Страница 5: ...a chemical reaction triggered by moisture between the foil and the galvanized sheets Then consider covering the unit with tarpaulin to protect it The unit is delivered fully tested and ready for opera...

Страница 6: ...propriate use The unit must not be used for extraction of shavings or shreds or where there is a risk of explosive gases No duct connection If one or more of the spouts are not connected to a duct a p...

Страница 7: ...t it comes close to 100 This means that the need for heat supply during the cold winter months is reduced to a minimum and significant savings are achieved on the building s energy consumption and a r...

Страница 8: ...binet 12 Valves for refrigerant manometer 13 Pipe for flow return to water after heating element see picture14 a flow b return 14 After heating element water electricity accessory see picture 14 15 Co...

Страница 9: ...or a left facing version All measurements are in mm 180 600 1480 600 85 75 800 285 285 80 15 75 85 600 600 180 800 285 285 1370 950 2000 950 3910 140 330 600 1050 1225 50 Supply air supply Extract air...

Страница 10: ...ned drawing below is for a left facing version All measurements are in mm 1370 130 800 800 160 1000 100 270 160 800 2000 800 130 1000 270 100 1140 2000 1140 4290 135 550 650 1210 1415 50 Supply air su...

Страница 11: ...for a left facing version All measurements are in mm 1215 2000 1215 4440 1910 140 800 800 205 205 800 2100 800 140 1200 355 355 155 1200 355 355 155 130 650 750 1315 1490 50 Supply air supply Extract...

Страница 12: ...g below is for a left facing version All measurements are in mm 1370 2100 1370 4850 1910 260 1000 1000 230 230 1000 2660 1000 260 1400 255 255 170 1400 255 255 170 150 770 970 1470 1620 50 Supply air...

Страница 13: ...100x25 4 grey 100x100x25 Without base 4 red 100x100x25 8 brown 100x100x25 Placed both front and rear VPM 1200 1500 600kg 1200kg 600kg VF VP BB With base 4 grey 120x120x25 4 red 120x120x25 Without base...

Страница 14: ...air 2 Supply air 3 Extract air 4 Discharge air 5 Condensate drain 6 Electrical and water after heating element Automation T1 Outdoor air sensor T2 T7 Supply air sensor T9 After heating element frost p...

Страница 15: ...replacing at the final pressure drop that has been preset in the CTS control system Humidity control A humidity control system can be added to the unit to control ventilation according to the relative...

Страница 16: ...r frost protection of the condensate drain of 3m and 5m respectively Used in cases where Nilan water trap with ball is mounted and where it is not possible to use the integrated heating cable The 10W...

Страница 17: ...a pallet each before you lift them with a pallet jack Lift with transport hooks in pre assembled lifting eyes The VPM 600 3200 is equipped with lifting eyes If chains or straps are used directly on t...

Страница 18: ...s X X Recommended service distance Unit X in mm VPM 600 750 VPM 700 750 VPM 800 750 VPM 1000 750 VPM 1200 800 VPM 1500 800 VPM 2200 950 The unit must be level to enable proper drainage from the conden...

Страница 19: ...sired place Step 2 The vibration dampers sylomes are placed under the adjusting screws a Nilan base b Adjusting screws c Sylomer Step 3 Base is adjusted a This section is for the discharge module and...

Страница 20: ...ck of space a lifting beam or similar must be used See the section Transport after unpacking for proper handling NB The VPM600 is delivered on a firm base Step 5 The enclosed sealing tape is pasted on...

Страница 21: ...are tightened and the sections are pulled together After installation the square grooves are filled with silicone a Brackets b Bolt Step 8 The modules are now screwed together with the supplied steel...

Страница 22: ...atcher is mounted in the VPM module a Drop catcher b Evaporator c Condensate tray d EC Fan Filter fan unit Middle section Step 10 If the unit comes with a discharge module repeat the steps for the dis...

Страница 23: ...ely to the ground It is possible to buy a storm bracket from Nilan article number 77223 The bracket attaches the unit together with the base a Opel screws 6 3 x 19 with washer Drill with 4 5 mm bit b...

Страница 24: ...res are not damaged or trapped during connection and use Connections overview All electrical connections are located on front of the unit 1 Connection of power supply cable for VPM 2 Cable grommets fo...

Страница 25: ...surface 3x400V 50HZ Ampere consumption depending on selected compressor and fans Unit Compressor Fan 2 motors total MTZ VTZ at 500 Pa at 1000 Pa Amp Amp Amp Amp VPM 600 21 21 4 0 6 2 VPM 700 24 24 4 4...

Страница 26: ...3 meter Cat 5e cable of the type 4x2x0 5mm twisted pair If you want a longer cable use a standard LAN cable maximum length 50 meters If you want to extend the cable length please be aware of the foll...

Страница 27: ...ration of the unit The wall bracket is located at the back of the panel You can detach it by loosening the bracket at the bottom of the panel You can then remove it Mount the wall bracket on the wall...

Страница 28: ...it board should be done in accordance with the wiring diagram The electrical after heating element type EB for the VPM 600 2200 series comes built into the unit if you have opted to have this added Th...

Страница 29: ...nit from the factory if purchased together with the unit If the water after heating surface is retrofitted the connection of the circulation pump must be carried out by an authorized electrician Red B...

Страница 30: ...e if the condensate tray overflows and condensate water runs out of the unit The water trap may dry out which would prevent water from draining from the condensate tray as air would blow into the unit...

Страница 31: ...with 32 mm spout 2 Reducing fitting for 20 mm 3 Reducing fitting for RG 4 Reducing fitting for tube Dimensional drawing All measurements are in mm 100 90 225 76 162 32 32 32 20 123 For commercial plan...

Страница 32: ...AME 140 24V circulation pump eg Grundfoss UPS 25 40 or equivalent control valve 3 way valve auto transformer dirt collector as well as shut off venting bypass drain fill valve Connect up the system ve...

Страница 33: ...1500 31 4 12 3 0 2 4 6 355 0 8 3000 26 1 19 1 0 5 14 4 552 1 5 4500 23 3 24 2 0 7 28 1 698 2 3 6000 21 4 28 3 0 9 45 0 817 3 1 50 30 1500 29 1 11 1 0 4 4 6 480 0 8 3000 24 6 17 5 0 8 14 4 755 1 5 4500...

Страница 34: ...9 9 1759 1 3 9000 24 6 52 6 10 6 19 3 2272 1 9 12000 22 8 62 4 14 4 30 9 2697 2 5 15000 21 5 70 9 18 1 44 6 3063 3 1 The heating element has two rows of pipes and a 1 RG connection Regulation valve a...

Страница 35: ...Regulation valve accessory Add when ordering VPM 600 2200 English BY NILAN 35...

Страница 36: ...nced correctly Nilan A S recommends that this is done by professionals If a pressure control system has been purchased additionally set the duct pressure in the pressure control boxes when balancing t...

Страница 37: ...ce curves Capacity Curve Pressure drop water coil Pa SFP J m3 2500 VPM 800 1000 Assessment of SEL value at various airflow pressure losses 1200 1800 2100 2500 0 100 200 300 400 500 600 700 800 900 100...

Страница 38: ...rop Pa qV m3 h Capacity Curve Pressure drop water coil Pa SFP J m3 VPM1200 Air performance curves VPM 1500 Assessment of SEL value at various airflow pressure losses 1200 1800 2100 2500 0 200 400 600...

Страница 39: ...ressure losses 1200 1800 2100 2500 0 200 400 600 800 1000 1200 1400 1600 3000 8000 13000 18000 23000 Pt External pressure drop Pa qV m3 h VPM2200 Air performance curves Capacity Curve Pressure drop wa...

Страница 40: ...f the unit under normal operating conditions Maintenance of the unit should be adapted to fit the actual operating conditions Component Action Once a year In case of alarm Filters Replacement of filte...

Страница 41: ...eplacement Filters should however be replaced at least every three months Always record dates of filter replacements so that intervals between these can be easily monitored and observed Be aware of th...

Страница 42: ...00 Type Numbers per air line Nilan article number ISO ePM10 60 filter M5 2 3913 ISO ePM1 50 filter F7 2 39042 Filters VPM 1200 1500 Type Numbers per air line Nilan article number ISO ePM10 60 filter M...

Страница 43: ...VPM 600 2200 English BY NILAN 43...

Страница 44: ...tions or for loss or damages arising from published materials whether these are due to errors or inexpediency in the publications or they have other causes Without prior notice Nilan A S reserves the...