nilan CTS6000 Скачать руководство пользователя страница 5

User's Guide for CTS6000 Control panel 

 

Version 1.00 

Subject to alteration without notice.  

NILAN A/S 

Page 5 of 11  

Power button 

 
 
 
 
 
 
 
 
 

 

Figure 5 Power, System in Operation

 

 

Pressing the "POWER" button opens the menu shown in Figure 5. "Stop system" is used to stop 
the system or to start it in weekly program mode. If "Stop system" is selected the unit will remain 
stopped and NOT follow the weekly program. 
If "Start extended operation" is selected, the unit will continue to run for an additional 2 hours (the 
duration can be changed via CTS6000 WebControl). 
 
 

Weekly program 

The  control  panel  can  be  used  to  change  the  required  temperature  and  start/stop  times  in  the 
weekly  program  (setpoints  for  fan  speed  or  duct  pressure  can,  however,  only  be  changed  via 
CTS6000 WebControl). 
The weekly program is opened from the startup display by pressing arrow up or arrow down. The 
menu  shown  in  Figure  2  will  then  appear.  Use  arrow  up  or  arrow  down  to  select  "WEEKLY 
PROGRAM" 
Then press arrow right to open the weekly program, see Figure 6.  
 
Use  arrow  up  or  arrow  down  to  scroll  through the  various  menu  options for the  day  selected. As 
standard,  Monday  is  initially  displayed  when  the  weekly  program  is  opened.  Six  program  events 
can be defined for each day of the week. Figures at the top of the display indicate the number of 
events  defined  for  the  day  in  question.  For  each  program  event  in  which  the  unit  is  in  operation 
(Program  Event:  Active),  it  is  possible  to  change  the  required  settings,  see  Figure  6.  To  do  so, 
select the setting to be changed, press SET to change the setting, press arrow up or arrow down to 
select the required value and then press SET to save the new setting. 
To  select  another  day  of  the  week,  highlight  Monday,  press  SET,  select  the  required  day  of  the 
week using the arrow up or arrow down buttons and then press SET again once the required day 
has been highlighted.  
 
 

 
 
 
 
 
 
 
 
 

 

Figure 6 Weekly program

 

 

 

PROGRAM EVENT : 

ACTIVE 

TIME :   

 

 

 

17:00 

VENTILATION : 

 

HIGH, STD 

SETPOINT :  

 

 

20.0

 

COPY TO NEXT 

 

No

 

EXIT 

SET = CHANGE 

Monday 
PROGRAM : 

1 2 3 - 

 

POWER 

STOP SYSTEM 

 

START EXTENDED 

OPERATION 

All manuals and user guides at all-guides.com

Содержание CTS6000

Страница 1: ...User s Guide CTS6000 control panel Version 1 03 2014 06 25 Valid for SW version 1 0088 All manuals and user guides at all guides com a l l g u i d e s c o m ...

Страница 2: ...oint menu 6 Menu overview 9 Description of alarms 10 Figure Figure 1 Panel startup display 4 Figure 2 Menue 4 Figure 3 Alarm log with new alarm 4 Figure 4 Alarm log with no alarm 4 Figure 5 Power System in Operation 5 Figure 6 Weekly program 5 Figure 7 Selecting the manual set point mode 6 Figure 8 Manual mode parameters setting 7 Figure 9 Manual mode parameters setting 7 Figure 10 Java GUI manual...

Страница 3: ... operation to be viewed and altered It is thus possible to change various temperature settings reset alarms and start the unit outside the usual operating period The CTS6000 control panel supplements CTS6000 WebControl the program in which more advanced settings are made A menu overview and descriptions of all alarms can be found at the end of the guide All manuals and user guides at all guides co...

Страница 4: ...tup display Figure 2 Menue The startup display reappears if no button is pressed for 15 seconds Alarm log event log The alarm log is accessed by pressing the ALARM button i e the one marked with a bell on the bottom right of the panel The most recent alarms events will then be displayed see Figure 3 It is possible to scroll through previous alarms events using the arrow up and down buttons Figure ...

Страница 5: ...hen press arrow right to open the weekly program see Figure 6 Use arrow up or arrow down to scroll through the various menu options for the day selected As standard Monday is initially displayed when the weekly program is opened Six program events can be defined for each day of the week Figures at the top of the display indicate the number of events defined for the day in question For each program...

Страница 6: ...access the service menu activate the control panel by pressing arrow down Then press and hold SET for approx 10 seconds The service menu will then appear Manuel Set point menu To enter the manual set point mode one should hold power button until the corresponding menu appears see Figure 7 Selecting the manual set point mode After selecting the mode one is able to adjust manual mode parameters see ...

Страница 7: ...ter 2 Parameters editing a Button SET start of value editing b Buttons Up Down change a value 1 1 c Button Left cancel editing d Button SET store a changed value 3 Return back from menu sub menu Button Left After the new week program begins the system automatically switches to auto mode turning the manual mode off Figure 8 Manual mode parameters setting Figure 9 Manual mode parameters setting All ...

Страница 8: ...User s Guide for CTS6000 Control panel Version 1 00 Subject to alteration without notice NILAN A S Page 8 of 11 Figure 10 Java GUI manual mode in PI Diagram All manuals and user guides at all guides com ...

Страница 9: ... 23 7 C ANALOG1 100 ANALOG2 100 ANALOG3 000 ANALOG4 000 ANALOG5 000 ANALOG6 100 MONDAY PROGRAMME 1 2 PROGRAM POINT AKTIVE TIME 17 00 VENTILATION NORMALE SET POINT 20 0 COPY TO NEXT NO Week programme Date Time Language Unit Information Min Sommer Regulation Change Present Language Change Network IP Min Winter Netmask Max Sommer Winter Week Programme Restart Unit LA SORTIE SET CHANGE Date Time Statu...

Страница 10: ...hour however Condenser high pressure ID 8 11 Level 4 Upper limit 2 for cooling circuit pressure set under Pressure limits has been exceeded The alarm can be activated by insufficient air flow through the unit This may be caused by blocked filters loose V belts or dampers which have not opened Reset alarm If the alarm repeatedly occurs for no apparent reason call service Evaporator low pressure 1 I...

Страница 11: ...utes and reset the alarm Pressure pipe temperature T10 11 12 13 ID 50 51 52 53 Level 2 Pressure pipe temperature on compressor 1 2 3 4 has exceeded 125 C The controls stop the compressor and do not allow it to restart before the temperature has dropped below 50 C If the alarm repeatedly occurs call service VLT x has not responded to the 5 latest requests ID 111 Level 4 A communication error has oc...

Отзывы: