35
114
TColdRet Open
T14 Cold return temperature open connec
-
tion.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
115
TColdRet Short
T14 Cold return temperature short-cir
-
cuited.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
116
Tevap Open
T23 Evaporator sensor temperature open
connection.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
117
Tevap Short
T23 Evaporator sensor temperature short
-
circuited.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
122
Tmixing Open
Tmixing temperature sensor open connec
-
tion.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
123
Tmixing Short
Tmixing temperature sensor shortcir
-
cuited.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
124
SHW T-sensor Open
T21 Temperature sensor in SHW opne con
-
nection.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
125
SHW T-sensor Short
T21 Temperature sensor in SHW shortcir
-
cuited.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
126
SHW anode
SHW anode failure.
The anode must be changed.
127
TPres open
T35 Temprerature sensor Pressure open
connection.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
128
TPres short
T35 Temperature sensor Pressure short
-
circuited.
Check cable and connectors.
Measure the resistance in the temperature
sensor.
200
LOM309 missing
Controller is not Extended version
Functionality of Extended version is
selected.
Exchange controller to the Extended ver
-
sion or disable use of this functionality.
600
Hi Pres
High pressure switch active.
Check hot side pump/overflow valve on
high temperature side. Check if there is air
in the hot side water. Check if filter is
blocked on the hot side.
The unit restarts when the pressure drops
below high pressure switch lowlimit again.
After 3rd cut-out the alarm must be
acknowledged to start the unit again.
601
Low pres.
Low pressure switch active.
Check refrigerant charge, expansion valve
and evaporator for ice. Check fan for
obstacles on an air to water evaporator.
The alarm must be acknowledged to start
the unit again.
602
Leakage
Low pressure in brine - Brine pressure
switch active.
Leakage check of the brine system.
The alarm must be acknowledged to start
the unit again.
603
Hi press
High pressure switch repeatedly active.
Check hot side pump/overflow valve on
high temperature side.
The alarm must be acknowledged to start
the unit again.
604
Frost protection
Temperature too low (state freeze protect)
Heat pump and electrical heater running
full capacity.
Check that setting are not turned off.