25
Fire automation system
General information
Safety
It is important to check that wires are not damaged or squeezed during connection and use.
Usage
Nilan's fire automation system is used to monitor, test and check the fire protection components of the ventilation system:
• Fire and smoke damper, and fire thermostat
Important functions:
• Monitors the fire protection system and ensures that dampers and detectors are in fully working order
• Tests dampers every 7th day - set for Mondays 10.00 a.m.
• If fire is detected, fire and smoke dampers will close and the ventilation unit will stop
• If the ventilation unit stops, fire and smoke dampers will close
Dampers that are connected up to the system must have a 24V or 230V fire damper motor.
The fire automation system is for indoor installation. The automation system can be used within a temperature range of -20 °C to
+40 °C. The protection level for fire and smoke dampers must be IP65
ATTENTION
All work must be carried out by suitably qualified persons and in compliance with existing legislation and regulations.
ATTENTION
It is important that the power is off if you do work to the electrical components of the ventilation unit.
WARNING
Must not be used as a fire alarm system.