21
Maintenance and service guide - LSN-FLSN ZONE
2 - Ex ec
5724 en - 2020.02 / c
INSTALLATION AND MAINTENANCE – LSN-FLSN ZONE 2 – Ex ec
9.6.4 - Connections
- Connection of auxiliaries on the three-pole Bartec
terminal strips ref. 07-9702-0320/1 (AECE: PTB99 ATEX
3117 U - IECEx PTB 07.0007U) provided for auxiliaries
(sensors, heaters etc.).
:
* max tightening torque: 0.4 N.m
* max total cross-section per connection: 2.5 mm²
* Umax = 440V - Imax = 23A for example
* Min air gaps = 8
- Positioning of power connection connectors (in “eb” and
“ec” box)
Positioning of stator power supply cables on the terminal
block
Stator
cables
Terminal
block
Connection
bar
Client
cables
Heat-shrink
sleeving
Crimped
connectors Lock-nut
Cables must be parallel with each other
in order to ensure that the 14 mm air-gap distances
between phase and between phase and earth are achieved.
For FLSN motors with frame sizes 250 to 355 (terminals
M10 and M12), the stator supply cable cross-section must
be 35 mm² minimum.
Creepage distances and air gap requirements must be
observed and must comply with the requirements of standard
IEC/EN 60079-7 for the assigned voltage.