38
DFS1/DFS2 Power Installation Guide
Issue Number: 2
A maximum operating ambient temperature of 35 °C is assumed at a maximum altitude of 1000 m
and 2 kHz switching frequency. Derating is required for higher switching frequencies, ambient
temperatures and altitudes.
Table 4-3 Incoming supply cable sizes and connections
Motor cable sizes
The nominal output cable sizes assume that the motor maximum current matches that of the drive.
Where a motor of reduced rating is used the cable rating may be chosen to match that of the motor.
To ensure that the motor and cable are protected against over-load, the drive must be programmed
with the correct motor rated current.
The number of cables is always 1 or 2 per installed power module
Model
Input
current
A
Cable size
(mm²)
Incomer switch
MCCB type
(Schneider)
Connection
Connectable cable
sizes
xxxx-DFS1G4EN
155
1 x 50
NSX250
Bar, with 1 x 9 mm
hole
1 or 2 cables up to
150 mm², with
M8 lug
xxxx-DFS1H4EN
177
1 x 70
xxxx-DFS1J4EN
232
1 x 95
NSX400
Bar, with 1 x 11 mm
hole
1 or 2 cables up to
240 mm², with
M10 lug
xxxx-DFS1K4EN
267
1 x 95
xxxx-DFS1L4EN
332
1 x 150
xxxx-DFS1M4EN
397
1 x 185
NSX630
xxxx-DFS1N4EN
449
1 x 240
xxxx-DFS1P4EN
492
2 x 95
xxxx-DFS1Q4EN
539
2 x 120
xxxx-DFS2L4EN
631
2 x 150
NS800
Bar, with 3 x 11 mm
hole two holes are
usable with large
lugs
1 to 4 cables up to
240 mm², with
M10 lug
xxxx-DFS2M4EN
657
2 x 150
xxxx-DFS2N4EN
853
2 x 240
NS1000
xxxx-DFS2P4EN
935
3 x 150
xxxx-DFS2Q4EN
1024
3 x 150
NS1250
xxxx-DFS166EN
83
1 x 16
NSX160
Bar, with 1 x 9 mm
hole
1 or 2 cable up to
150 mm², with
M8 lug
xxxx-DFS176EN
104
1 x 25
xxxx-DFS186EN
149
1 x 50
NSX250
xxxx-DFS196EN
171
1 x 50
xxxx-DFS1A6EN
202
1 x 70
xxxx-DFS1B6EN
225
1 x 95
xxxx-DFS1C6EN
256
1 x 95
NSX400
Bar, with 1 x 11 mm
hole
1 or 2 cables up to
240 mm², with
M10 lug
xxxx-DFS1D6EN
302
1 x 120
xxxx-DFS1E6EN
329
1 x 150
xxxx-DFS2A6EN
384
1 x 185
NSX630
xxxx-DFS2B6EN
427
1 x 240
xxxx-DFS2C6EN
486
2 x 95
xxxx-DFS2D6EN
574
2 x 120
xxxx-DFS2E6EN
625
2 x 150
NS800
Aluminium
connection block
required for supply
voltage > 500 V
1 to 4 cable up to
240 mm²,
bare cables