10.4 Emission compliance
The drive contains an in-built filter for basic emission control. An additional optional external filter provides further reduction of emission. The
requirements of the following standards are met, depending on the motor cable length and switching frequency.
Table 10-4 Emission compliance
This is a summary of the EMC performance of the drive and the guidelines in
section 4.7.1 EMC compliant installation
should
be adhered to. For full
details, refer to the EMC Data Sheet which can be obtained from the supplier of the drive.
Drive Model
Number
Power Rating
Motor Cable
Length
Using Internal Filter Only
Using Internal and External Filter
kW
hp
4 kHz
12 kHz
4 kHz
12 kHz
100 V Drive (100 to 120 V ±10 %)
S100-01113
0.18
0.25
S100-01123
0.25
0.33
S100-01133
0.37
0.5
S100-03113
0.55
0.75
S100-03123
0.75
1
S100-03133
1.1
1.5
200 V Drive (200 to 240 V ±10 %)
S100-01S13
0.18
0.25
S100-01213
0.18
0.25
S100-02S11
0.18
0.25
S100-01S23
0.25
0.33
S100-01223
0.25
0.33
S100-02S21
0.25
0.33
S100-01S33
0.37
0.5
S100-01233
0.37
0.5
S100-02S31
0.37
0.5
S100-01S43
0.55
0.75
S100-01243
0.55
0.75
S100-02S41
0.55
0.75
S100-01S53
0.75
1
S100-01253
0.75
1
S100-02S51
0.75
1
S100-01D63
1.1
1.5
S100-02S61
1.1
1.5
S100-01D73
1.5
2
S100-02S71
1.5
2
S100-03D13
2.2
3
400 V Drive (380 to 480 V ±10 %)
S100-02413
0.37
0.5
S100-02423
0.55
0.75
S100-02433
0.75
1
S100-02443
1.1
1.5
S100-02453
1.5
2
S100-02463
2.2
3
S100-03413
3
3
S100-03423
4
5
This is a product of the restricted distribution class according to IEC 61800-3. In a residential environment this product may cause radio
interference in which case the user may be required to take adequate measures.
Residential generic standard IEC 61000-6-3.
EN 61800-3:2018 first environment unrestricted distribution
EN 61800-3:2018 defines the following:
•
The first environment is one that includes residential premises. It also includes establishments directly connected without
intermediate transformers to a low-voltage power supply network which supplies buildings used for residential purposes. The second
environment is one that includes all establishments other than those directly connected to a low-voltage power supply network which
supplies buildings used for residential purposes.
•
Restricted distribution is defined as a mode of sales distribution in which the manufacturer restricts the supply of equipment to
suppliers, customers or users who separately or jointly have technical competence in the EMC requirements of the application of
drives.
IEC 61800-3:2018 and EN 61800-3:2018