![Nidec Commander C200 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/nidec/commander-c200/commander-c200_step-by-step-manual_1687775006.webp)
6
C200/C300 Step By Step Guide
Issue Number: 1
STEP 5: Remove the terminal cover
1.
Using a flat bladed screwdriver, turn the terminal cover locking clip anti-clockwise by approximately 30°.
2.
Slide the terminal cover down.
3.
Remove terminal cover in direction shown.
STEP 6: Wire the drive up
Power connections
When wiring the drive the power, ground and control connections, they should be ightened to the recommended
torque settings shown in the table below:
Table 6-1 Recommended torque settings
Connect the supply and motor connections using the cables and fuses or MCB's quoted in the table
shown in Step 4.
When using a single phase supply, he supply should be connected to L1 and L3.
Figure 6-1 Power terminal connections
Model size
Terminal block description
Torque settings
All
Control terminals
0.2 N m (0.15 Ib ft)
Relay terminals
0.5 N m (0.37 Ib ft)
1
Power terminals
0.5 N m (0.37 Ib ft)
2, 3, 4
1.4 N m (1.03 Ib ft)
All
Ground terminals
1.5 N m (1.10 Ib ft)
2
3
1
L1
L2
L3
1 ph /3 ph
*
AC power
supply
U
V
W
AC supply
Motor
L1/Live
L2
L3/Neutral
Ground