NICOR LED EMB4001UNV Series Скачать руководство пользователя страница 2

NICOR, Inc.   2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393  www.nicorlighting.com July 22, 2021 9:58 AM

•  Carefully unpack EMB400 from packaging. Inspect product 

for defects due to shipping.

•  Turn off power to appropriate circuit at the breaker box.

Installation

1

EMB4001UNV** 

INSTALLATION INSTRUCTIONS

Installation of Battery Pack

•  Select a suitable location on the ceiling for mounting.
•  Install the hook (1) to the top of the EMB400 (2) and lock 

with set screw. 

•  Install the ring (7) to the bottom of the EMB400 (6) and lock 

with set screw.

•  Open the cover of junction box (4). Cover has safety cable.
•  Hook the EMB400 to a suitable hanging device secured to 

structure. 

•  Hang the fixture (8) to the ring of the EMB400.  Lock down 

safety screw.

•  Install the BX cables on AC wires and dimming wires (3) per 

the wiring diagram. 

2

Wiring of Battery Pack

•  Use the wiring diagram as reference.
•  Connect the AC power source leads (Switched and 

Unswitched) to the input of the EMB400.

•  Connect the output leads of the EMB400 to the Fixture
•  Wire the fixture in accordance with manufacturer’s 

installation instructions.

•  Make sure all connections are in accordance with the 

National Electrical Code and any local regulations.

•  In a readily visible location, attach the label 

“CAUTION: 

This unit has more than one power connection point. 
To reduce the risk of electric shock, disconnect both 
the branch circuit breakers/fuses and disable EM 
output before servicing. Disable output by holding the 
test switch down for 3 seconds while the EMB400 is 
operating in emergency mode.”

3

Complete Installation

•  After installation is complete, apply AC power .
•  The Charging Indicator Light should illuminate indicating 

the battery is charging.

•  A short-term discharge test may be conducted after the 

backup nano inverter has been charging for 1 hour.

•  Charge for 24 hours before conducting a long-term 

discharge test.

4

White(Common)

Black / White

1

2

3

4

6

7

5

3

8

EMB400

HO
T (100~277V

)

Pur

ple ()

Gr

ay (Dimmer -)

W

hit

e (

Common)

Black/W

hit

e

Black (L)

W

all S
wit
ch

Gr

een (

GND

)

Red

 

DIM+

Yello
w

 

DIM
-

Blue               

W

hit

e

Br

own           Black

Luminaire

Dimmer 

or

Sensor

NOTE: 

Dimming leads from 

EMB400 to LED Driver must 

be attached to the DIM+ and 

DIM- wires of the luminaire 

regardless of the use of any 

other sensors or control 

systems. 

Отзывы: