![NICOR LED EMB4001UNV Series Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/nicor/led-emb4001unv-series/led-emb4001unv-series_installation-instructions_1687711002.webp)
NICOR, Inc. 2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393 www.nicorlighting.com July 22, 2021 9:58 AM
• Carefully unpack EMB400 from packaging. Inspect product
for defects due to shipping.
• Turn off power to appropriate circuit at the breaker box.
Installation
1
EMB4001UNV**
INSTALLATION INSTRUCTIONS
Installation of Battery Pack
• Select a suitable location on the ceiling for mounting.
• Install the hook (1) to the top of the EMB400 (2) and lock
with set screw.
• Install the ring (7) to the bottom of the EMB400 (6) and lock
with set screw.
• Open the cover of junction box (4). Cover has safety cable.
• Hook the EMB400 to a suitable hanging device secured to
structure.
• Hang the fixture (8) to the ring of the EMB400. Lock down
safety screw.
• Install the BX cables on AC wires and dimming wires (3) per
the wiring diagram.
2
Wiring of Battery Pack
• Use the wiring diagram as reference.
• Connect the AC power source leads (Switched and
Unswitched) to the input of the EMB400.
• Connect the output leads of the EMB400 to the Fixture
• Wire the fixture in accordance with manufacturer’s
installation instructions.
• Make sure all connections are in accordance with the
National Electrical Code and any local regulations.
• In a readily visible location, attach the label
“CAUTION:
This unit has more than one power connection point.
To reduce the risk of electric shock, disconnect both
the branch circuit breakers/fuses and disable EM
output before servicing. Disable output by holding the
test switch down for 3 seconds while the EMB400 is
operating in emergency mode.”
3
Complete Installation
• After installation is complete, apply AC power .
• The Charging Indicator Light should illuminate indicating
the battery is charging.
• A short-term discharge test may be conducted after the
backup nano inverter has been charging for 1 hour.
• Charge for 24 hours before conducting a long-term
discharge test.
4
White(Common)
Black / White
1
2
3
4
6
7
5
3
8
EMB400
HO
T (100~277V
)
Pur
ple ()
Gr
ay (Dimmer -)
W
hit
e (
Common)
Black/W
hit
e
Black (L)
W
all S
wit
ch
Gr
een (
GND
)
Red
DIM+
Yello
w
DIM
-
Blue
W
hit
e
Br
own Black
Luminaire
Dimmer
or
Sensor
NOTE:
Dimming leads from
EMB400 to LED Driver must
be attached to the DIM+ and
DIM- wires of the luminaire
regardless of the use of any
other sensors or control
systems.