INSTALLATION INSTRUCTIONS
the set Ambient Light Level. Set the Band Switch to OCC or AUTO
mode. The Load will turn on only if motion is detected and the Ambient
Light Level also below the set light level.
Note: Use ambient light feature when daylight source is available.
Back to factory default(daylight)
Set the Band Switch to VAC, press and hold the Manual ON/OFF
Button for 6 seconds till the Load turns on, continue holding the button for
another 5 seconds until the Load turns off, then release the button and
set the Band switch to OCC or AUTO Mode, it confirms that the sensor
switch goes back to factory default.
+ OPERATION
The Sensor Switch can be used independently for any mode
(AUTO, OCC, or VAC) as set by the Band Switch position under the
control panel cover. Some might call the Vacancy mode, "Manual On
Occupancy Mode."
Manual On/Off Button
By Pushing the Control Panel Cover, the Load can be turned On/Off
under either OCC or VAC mode (illustrated in Figure 5).
Occupancy Mode - Auto on, Auto Off
Load will be Automatically On once occupancy is detected.
Vacancy Mode - Manual On, Auto Off
On/Off Button must be pushed to turn On the Load.
Automatic Off
Under any Mode, the sensor keeps the Load On until no motion is
detected plus the set time delay. Turns Off automatically.
Manual Off
By pushing the Manual On/Off button, the Load can be turned Off under
any Mode. Under AUTO/OCC Mode, the Load cannot be automatically
turned On for 5 minutes after the last motion is detected.
-04-
- .
• 0
Figure 5
Auto Set Occupancy Mode
Automatically set the time delay between 7 to 30 minutes based on occupancy
patterns. Auto set behavior starts right after the time delay knob is
turned away from Test Mode. Includes the walk-through mode.
Walk-Through Mode
In case of walk-through, the Load automatically turns On and then turns
Off 2.5 minutes after a brief occupancy moment of 30 seconds. If
motion is detected within the first 30 seconds and also continues in the
coming 2.5 minutes, Auto Set Occupancy Mode applies.
+ TROUBLESHOOTING
For proper operation, the Sensor Switch has to consume power from
hot and
Ground
Therefore, a
Secured Ground Wiring is required.
Initialization
The Sensor Switch needs to initialize for 3 munites. During the
initialization the load might be turned On and Off several times.
The Time Delay knob is set to 15 seconds by default, do not adjust it until
initialization is completed and proper operation confirmed.
The Load is out of control (frequently flashing)
1. It can take up to three minutes for initial run.
2. Check the wiring connections, especially the Ground Wiring.
The Load does not turn On without LED flashing or LED flashes
regardless of motion
1. Push Manual On/Off Button. If the load turns On, verify that the Sensitivity
Range is on high. If the Load does not turn On, go to Step 2.
2. Check the wiring connections.
The Load does not turn On while LED flashes with motion detected
1. Check to see if Ambient Light Level is enabled by covering the lens
by hand.
2. Push Manual On/Off Button If the load turns On, verify that Sensitivity
Range is on high. If the Load does not turn On, go to Step 3
3. Check the wiring connections, especially Hot Line and Ground wiring.
The Load does not turn Off
1. There can be up to a 30 minute time delay after the last motion is
detected. To verify proper operation, turn the Time Delay Knob to 15s
(Test Mode) and make sure there is no motion (no LED flashing).
The Load should turn Off in 15 seconds.
-05-
2. Check if there is any significant heat source mounted within six feet (two
meters) that may cause false detection such as a high wattage light bulb,
portable heater, or HAVC device.
3. Check the wiring connections, especially the Ground wiring to the
sensor switch.
The Load turns On when not desired
1. Mask the Sensor Switch lens to eliminate unwanted coverage area.
2. Turn the Sensitivity Level knob toward left to avoid false alert in
a small room and when near a doorway.
3. Set the Band Switch to the VAC positon.
NICOR, Inc. 2200 Midtown Place NE, Albuqueruqe, NM
87107 www.nicorlighting.com P: 800.821.6283 F:
800.892.8393