1 - GENERAL WARNINGS: SAFETY - INSTALLATION - USE

 

 

(Instructions translated from Italian)

CAUTION

Important safety instructions. Follow all instructions as improper installation 

may cause serious damage

CAUTION

Important safety instructions. It is important for you to comply with these in-

structions for your own and other people’s safety. Keep these instructions

Before commencing the installation, check the “Product technical specifications”, in particular whether 

this product is suitable for automating your guided part. If it is not suitable, DO NOT continue with the 

installation

Before proceeding with the installation of the product, check that all materials are in good working order 

and suited to the intended applications

The product is not intended for use by persons (including children) with reduced physical, sensory or 

mental capacities, nor by anyone with insufficient experience or familiarity

Children must not play with the appliance

Do not allow children to play with the control devices of the product

CAUTION

In order to avoid any danger from inadvertent resetting of the thermal cut-off device, 

this appliance must not be powered through an external switching device, such as a 

timer, or connected to a supply that is regularly powered or switched off by the circuit

Provide a disconnection device (not supplied) in the plant’s mains power supply, with a contact opening 

distance that permits complete disconnection under the conditions dictated by overvoltage category III

Handle the product with care during installation, taking care to avoid crushing, denting or dropping it, 

or allowing contact with liquids of any kind. Keep the product away from sources of heat and naked 

flames. Failure to observe the above can damage the product, and increase the risk of danger or mal-

function. If this should happen, stop installation immediately and contact Customer Service

The manufacturer assumes no liability for damage to property, items or persons resulting from non-

compliance with the assembly instructions. In such cases the warranty for material defects is excluded

Before working on the system (maintenance, cleaning), always disconnect the product from the mains 

power supply

The packing materials of the product must be disposed of in compliance with local regulations

If the product is damaged do not try to fix it and please contact the Service Centre 

2 - PRODUCT DESCRIPTION AND INTENDED USE

• 

Barrier controls

• 

Gate and door controls

• 

Parking and traffic managing

 - Warning! All uses other than the described use and use in environmental conditions other 

than those indicated in this manual should be considered improper and forbidden!

3 - FUNCTIONAL SPECIFICATIONS

The inductive loops detector LP22 is a system used for detecting vehicles by 

means of inductive loops with the following characteristics:

• 

Evaluation of two loops

• 

Presence detection or directional detection

• 

Galvanic isolation between loop and electronic parts of the detector

• 

Automatic adjustment of the system after power up

• 

Continuous balancing of frequency drift

• 

Suitable for monitoring individual parking spaces

• 

No interference between loop 1 and 2 due to multiplexing.

• 

Sensitivity can be set regardless of the loop inductivity

• 

Occupied loop message reported by the LED indicator

• 

0V Relay contacts which serve as outputs

• 

Operating principle of the 2-channel relay with switchable jumper

• 

Indication of the loop frequency via LED

• 

Loop connection available for Diagnostics

In the design and installation of inductive loops, you 

should take into consideration the table opposite. 

A normal insulated copper wire, preferably with a 

cross-section of 1.5 mm

2

, can be used to create the 

loop.

Lay the cable,with the number of windings indicated 

in the table. The two cable ends must be intertwined 

(at least 20 times per meter) from the loop to the 

detector.

Table

Loop perimeter

number of windings

less than 3 m.

6

from 3 to 4 m.

5

from 4 to 6 m.

4

from 6 to 12 m.

3

over 12 m.

2

4 - PROGRAMMING

4.1 -  Sensitivity

The sensitivity setting determines for each channel the change in inductivity that a vehicle must cause in 

order to use the output of the detector.
The sensitivity setting is performed separately for each channel using the 2 DIP Switches (see table 1).

Table 1

Sensitivity level

Channel 1: DIP Switch 1 and 2 

Channel 2: DIP Switch 3 and 4

1 low

(0.64 % Δf/f)

2

(0.16 % Δf/f)

3

(0.04 % Δf/f)

4 high

(0.01 % Δf/f)

4.2 -  Frequency setting

The operating frequency of the detector can be adjusted in 2 levels by using the DIP Switch 5 (see table 2).

Table 2

Frequency

DIP Switch 5

Low

   

   

High

   

   

The permitted frequency range is between 30 kHz and 130 kHz. The frequency depends on the chosen 

frequency level, and the inductivity resulting from the geometry of the loop, the number of loops and the 

power supply line of the loop.

4.3 - Wait time and new adjustment

The hold time can be adjusted with DIP-switch 6. At the completion of hold time it will be displayed “free 

loop” and the detector calibrates automatically. The hold time starts with the occupation of the loop.

Table 3

Delay

DIP Switch 6

5 minutes

5'

5'/

Uninterrupted

5'

5'/

A new adjustment can be activated manually by changing the delay time.
When switching on the power supply voltage, the detector will adjust the loop frequency. If there are brief 

outages in voltage (< 0.1 s), no new adjustment will take place.

4.4 - Output function
• Presence detection

For presence detection, the DIP Switch 7 must be positioned to the left. In this position, by means of 

the relay 1 the presence on loop 1 is reported. With the DIP Switch 8, the output signal for the relay 2 is 

determined (see table 4).

Table 4

Output function

DIP Switch 7 - DIP Switch 8

Both channels perform presence detection

Channel 1 presence det.

Channel 2 output pulse

• Directional detection

If DIP Switch 7 is in the right position, two directional logics will be supported depending on the DIP Switch 

8 (see table 5).

Table 5

Output function

DIP Switch 7 - DIP Switch 8

Direction presence signal

Direction pulse output

The directional pulse is mainly used for counting systems, while the presence direction signal is used for 

door and barrier control systems.
The examples in table 6 explain the operation modes of the direction logics. The direction signal is sent 

via the relay of the first loop to be crossed, i.e. in the driving direction 1

➟ 

2 the signalling is done via the 

relay 1.

Table 6

DIP Switch 8

Single vehicle

1

2

1

2

1

2

1

2

1

2

Relay 1  Signal “on” 

Relay 1 

Pulse 

Relay 1  Signal 

“remains”

Relay 1  Signal “off”

Traffic column

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

1

2

Relay 1  Signal “on” 

Relay 1 

Pulse 

Relay 1  Signal 

“remains”

Relay 1  Signal 

“remains”

Relay 1  Signal “off”

Relay 1  Signal “on” 

Relay 1 

Pulse 

Relay 1  Signal 

“remains”

Relay 1  Signal “off”

Vehicle manoeuvring

1

2

1

2

1

2

1

2

1

2

Relay 1  Signal “on” 

Relay 1 

Pulse 

Relay 1  Signal “off”

Relay 2 

Pulse 

The direction signal in the opposite direction is generated in the 

same way.
In case of breakage or closure of a loop the operation switches to 

the “Presence detection” mode, until the fault has been fixed.
Through the relay of the loop channel without faults, the signal of 

presence is now emitted if the loop is occupied.