Settings
AA1-X3
AA1-SF1
AA1-X7
FQ10-BT30
ELECTRICAL ADDITION - MAXIMUM OUTPUT
The immersion heater output is divided into 7 steps, accord-
ing to the table.
The immersion heater can be set to a maximum of 9 kW. The
delivery setting is 9 kW.
You reconnect to 7 kW by transferring the white cable from
terminal block X3:13 to terminal block X7:23 on the immersion
heater board (AA1). (The seal on the terminal block must be
broken.)
Setting maximum output in the electric additional heat is
done in menu 5.1.12.
Power steps of the immersion heater
3x400V (maximum electrical output,
connected upon delivery 9 kW)
Max L3 (A)
Max L2 (A)
Max L1 (A)
Electricaladdi-
tion (kW)
0.0
0.0
0.0
0
0.0
8.7
0.0
2
7.5
7.5
0.0
3
8.7
8.7
0.0
4
7.5
7.5
8.7
5
8.7
8.7
8.7
6
15.7
7.5
8.7
7
15.7
15.7
8.7
9
3x400V (maximum electrical output,
connected to 7 kW)
Max L3 (A)
Max L2 (A)
Max L1 (A)
Electricaladdi-
tion (kW)
0.0
0.0
0.0
0
4.3
0.0
0.0
1
0.0
8.7
0.0
2
4.3
8.7
0.0
3
8.7
8.7
0.0
4
13
0.0
8.7
5
8.7
8.7
8.7
6
13
8.7
8.7
7
The tables display the maximum phase current for the relev-
ant electrical step for the indoor module.
If the current sensors are connected, the indoor module
monitors the phase currents.
NOTE
If the current sensors are not connected, the in-
door module performs a calculation of how high
the currents will be if the relevant power steps are
added. If the currents are higher than the set fuse
size, the power step is not allowed to cut in. See
chapter Load monitor on page 26.
EMERGENCY MODE
When the indoor module is set to emergency mode (SF1 is
set to
) only the most necessary functions are activated.
•
No hot water is produced.
•
The load monitor is not connected.
•
Fixed temperature in the supply line, see section Emer-
gency mode thermostat.
Power in emergency mode
The immersion heater’s output in emergency mode is set
with the DIP switch (SF1) on the immersion heater board
(AA1), according to the table below. The factory setting is 6
kW.
6
5
4
3
2
1
kW
off
on
off
off
off
off
2
off
on
off
on
off
off
4
off
on
off
on
off
on
6
on
on
on
on
off
on
9
1
2
3
4
5
6
ON
The image shows the dip-switch (AA1-SF1) in the factory
setting, that is 6 kW.
Emergency mode thermostat
The supply temperature in emergency mode is set using a
thermostat (FQ10-BT30). It can be set to 35 (preset, e.g.
underfloor heating) or 45 °C (e.g. radiators).
LEK
LEK
För markvärme!
För frånluftsvärme!
25
Chapter 5 | Electrical connections
NIBE VVM 500