Copper
VPBS 300
277
litre
Volume (no dedicated solar storage volume)
2
litre
Volume, charge coil
0.8
litre
Volume, solar coil
24
litre
Volume, expansion vessel
12.4
kWh
Heat content at 50 °C
470
litre
Equivalent amount of hot water (40 °C)
5
280
litre
Primary coil capacity, domestic water (60 °C to 40 °C)
282
litre
Solar coil capacity, domestic water (60 °C to 40 °C)
29
minutes
Heating time charge coil (10 °C to 60 °C)
4
1h52m
h/m
Heating time solar coil (10 °C to 60 °C)
6
85
°C
Max operating temperature
3/0.3
bar/MPa
Max pressure, primary side
5.5/0.55
bar/MPa
Max pressure, water heater
3/0.3
bar/MPa
Maximum pressure, solar coil
16/1.6
bar/MPa
Max water supply pressure
6/0.6
bar/MPa
Max design pressure
3.5/0.35
bar/MPa
Exp. vessle, tap water, charge pressure
6/0.6
bar/MPa
Expansion relief valve, setting
85
°C
Max temperature, heating fluid
7/0.7
bar/MPa
Max operating pressure, T&P-valve
95
°C
Max operating temperature, T&P-valve
F1145-6,8,10,12, F2030-7,9, F2040-8,12,16,
F1155-6,12,16, F2120-8,12,16
Compatible NIBE heat pumps
1
1800
mm
Height
1950
mm
Required ceiling height
2
600
mm
Width
600
mm
Depth
137
kg
Net weight
416
kg
Gross weight
081 082
Part No.
1
For ground source heat pumps, this recommendation applies to max. 10 °C brine temperature and 53 °C in the tank.
2
With the feet removed, the required ceiling height is approx. 1930 mm.
4
At primary flow temperature 80 °C and primary flow 1025 l/h.
5
At incoming temperatures 10 °C and hot water draining of 30 l/min.
6
At primary flow temperature 80 °C and primary flow 278 l/h.
Tested according to standard EN 12897:2016.
Energy labelling
NIBE
Supplier
VPBS 300 Cu
VPB 300 R
Model
C
C
Energy efficiency class
95
88
W
Heat loss
277
282
l
Volume
23
Chapter 4 |
Technical data
VPB/VPBS