Cold and hot water
Connecting cold and hot water
There must be a mixing valve if the temperature can ex-
ceed 60 °C.
The
e hose to the expansion vessel can be installed
in the plugged connection on the safety valve.
Connecting hot water circulation
Titanium MegaCoil 200 & 300 hav
e a connection that allows
hot water circulation.
To reduce the risk of bacterial growth in systems with
hot water circulation, the temperature of the circulating
water should not fall below 50 °C. There should not be
any non-circulatory hot water pipes. Adjust the hot water
system so that the temperature does not fall below 50°C
at the ends of the system.
Docking
Titanium MegaCoil 200 & 300 can be connected in several
ways, one of which is shown here.
Further option information is available at www.nibe.co.uk
and in the respective assembly instructions for the heat
pumps used.
Chapter 4 |
Pipe connections
13
different
Symbol key
Meaning
Symbol
Venting valve
valve
Non-return valve
Mixing valve
Safety valve
T&P valve
Tundish
Temperature sensor
Circulation pump
Particle
Pressure reduction valve
Motorized valve
3/4”x22 Elbow and drain cock (see p. 6)
Cold water inlet combination valve
Pressure reduction valve, check valve and
expansion relief valve (see p. 6)