Transport
S2125 must be transported and stored vertically.
Ensure that the heat pump cannot fall over during
transport.
Check that the heat pump has not been damaged during
transport.
Installation and
positioning
• Place the heat pump in a suitable location outdoors
to prevent any risk of the refrigerant flowing in through
ventilation openings, doors or similar openings in the
event of a leak. It must also not constitute a hazard
to people or property in any other way.
• If the heat pump is placed in a location where any re-
frigerant leak could accumulate, for example below
ground level (in a dip or low-lying recess), the installa-
tion must satisfy the same requirements that apply
for gas detection and the ventilation of engineering
rooms. Requirements regarding sources of ignition
must be applied where appropriate.
• Place S2125 outdoors on a solid level base that can
take the weight, preferably a concrete foundation. If
concrete slabs are used they must rest on asphalt or
shingle.
• The lower edge of the evaporator must not be lower
than the level of the average local snow depth. The
base should be at least 70 mm tall.
• S2125 should not be positioned next to noise-sensitive
walls, for example, next to a bedroom.
• Also ensure that the placement does not inconveni-
ence the neighbours.
• S2125 must not be placed so that recirculation of the
outdoor air is possible. Recirculation entails reduced
power and impaired efficiency.
• The evaporator must be sheltered from direct wind / ,
which negatively affects the defrosting function. Place
S2125 protected from wind / against the evaporator.
• Small amounts of condensation water, as well as melt
water from defrosting, may be produced. Condensa-
tion water must be led off to a drain or equivalent.
• Care must be exercised so that the heat pump is not
scratched during installation.
LEK
S2125
LEK
S2125
LEK
S2125
min 300 mm
min
70 mm
Do not place S2125 directly on the lawn or other non
solid surface.
If there is a risk of snow slip from roof, a protective roof
or cover must be erected to protect the heat pump,
pipes and wiring.
NIBE S2125 7
IT'S IN OUR NATURE
Good to know about
NIBE S2125