
Heating/cooling operation
The circulation pump (GP13) only runs in cooling mode.
The factory setting for the circulation pump speed is
MAX.
During heating operation (default) the mixing and re-
versing valves are closed as illustrated.
10
0
0
10
0
10
10
0
Shuntventil
Växelventil
Shuntventil
Växelventil
Värmeläge
Kylläge
Mixing valve
(QN18)
Reversing valve
(QN12)
When the reversing valve is open as illustrated below
cooling is activated. The shunt opens and closes depend-
ing on temperature.
10
0
0
10
0
10
10
0
Shuntventil
Växelventil
Shuntventil
Växelventil
Värmeläge
Kylläge
Mixing valve
(QN18)
Reversing valve
(QN12)
When cooling has been activated, heating operation
is blocked for two hours (factory setting) to prevent
self-oscillation between cooling and heating. If neces-
sary, the setting can be changed in menu 1.9.5.
15
GB
Содержание PCM 40
Страница 2: ......
Страница 13: ...13 SE...
Страница 24: ...24 GB...
Страница 35: ...35 DE...
Страница 46: ...46 NL...
Страница 47: ...47 Elschema Wiring diagram Elektrischer schalt plan Elektrisch schema...
Страница 48: ......
Страница 49: ......
Страница 50: ......
Страница 51: ......