Program settings
Program setting of SOLAR 40 can be performed via the
start guide or directly in the menu system.
Caution
Also see the Installer manual for
F1145/F1155/SMO 40.
Start guide
The start guide appears upon first start-up after heat
pump installation, but is also found in menu 5.7.
Menu system
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Menu 5.2 - system settings
1)
Activating/deactivating of accessories.
Select: solar heating
1) Applies to NIBE F1145/F1155.
Menu 5.2.4 - accessories
2)
Activating/deactivating of accessories.
Select: solar heating
2) applies to NIBE SMO 40.
Menu 5.3.4 - solar heating
Settings for solarheat
Default
Selection
Setting
Menu
8°C
1–40°C
start delta-T
5.3.4
4°C
0–40°C
stop delta-T
95°C
5–110°C
max. tank tem-
perature
125°C
80–200°C
max. solar pan-
el temp
no
yes/no
freeze protec-
tion
2°C
-20°C–20°C
anti freeze
temp
off
on/off
solar panel
cooling
110°C
80–200°C
start solar pan-
el cooling
Passive/Active recharging.
Default
Selection
Name
Menu
off
off/on
passive rechar-
ging
5.3.4
110°C
50–125°C
activation tem-
perature
50°C
30–90°C
deactivation
temperature
off
off/on
active rechar-
ging
40°C
8–60°C
activating dT
20°C
4–50°C
deactivating
dT
Menu 5.6 - forced control
Forced control of the different components in the heat
pump as well as in the different accessories that may be
connected.
EP30-AA5-K1: Activating the circulation pump (GP4).
EP30-AA5-K2: Activating solar panel cooling.
EP30-AA5-K3: Signal to three way valve (QN23).
EP30-AA5-K4: No function.
Menu 4.7 - holiday setting
Default
Selection
Name
Menu
off
on/off
solar panel
cooling
4.7
SOLAR 40 | GB
18