FIGHTER  310P  comprises  an  electric  boiler  with  a 
copper  lined  water  heater  and  a  heat  pump  which 
recovers energy from the ventilation air. The recovered 
energy is supplied to the heat pump. The heat pump 
must be installed in a ventilation system intended for 
mechanical exhaust air.
The  output  of  the  immersion  heater  is  max  8.0  kW 
(Supplied output of 6.0 kW).
When  the  exhaust  air  at  room  temperature  passes 
through  the  evaporator,  the  refrigerant  evaporates 
because of its low boiling point. In this way the heat in 
the room air is transferred to the refrigerant.
The refrigerant is then compressed in a compressor, 
causing the temperature to rise considerably.
The warm refrigerant is fed to the condenser, which is 
in  the  boiler  water.  Here  the  refrigerant  gives  off  its 
heat to the boiler water, so that its temperature drops 
and the refrigerant changes state from gas to liquid.
The  refrigerant  then  goes  via  filters  to  the  expansion 
valve, where the pressure and temperature are further 
reduced.
The refrigerant has now completed its circulation and 
returns to the evaporator.

System description

Frånluft 

Avluft 

Frånluft 

Avluft 

Poistoilma 

Kierrätetty ilma 

Frånluft 

Avluft 

Förångare 

Expansionsventil 

Kompressor 

Frånluftsfläkt 

Kondensor 

Elpatron 

Frånluft 

Avluft 

Förångare 

Expansionsventil 

Kompressor 

Frånluftsfläkt 

Kondensor 

Elpatron 

Frånluft 

Avluft 

Frånluft 

Avluft 

Förångare 

Expansionsventil 

Kompressor 

Frånluftsfläkt 

Kondensor 

Elpatron 

Avkastluften 

Avløpsluften 

Till F 310P/360P UK 1-fas 

Till F 310P/360P UK 1-fas 

Frånluft 

Avluft 

Det är denna som används i MOSen.

3

For Home Owners

FIGHTER 310P

LEK

C

When the room air has 
passed through the heat 
pump it is discharged. The 
temperature of the air has 
been significantly reduced 
as the heat pump has 
extracted the energy in the 
room air.

G

The air from the kitchen 
fan goes directly out into 
a separate duct.

B

The warm room 
air is fed to 
FIGHTER 310P

D

FIGHTER 310P supplies 
the house with both hot 
water and room heating.

E

Outdoor air is drawn into the house.

A

The warm room air is 
drawn into the air duct 
system.

F

Air is transported 
from rooms with 
outdoor air devices to 
rooms with exhaust 
air devices.

Principle of operation

System diagram

Extract air

Exhaust air

Содержание FIGHTER 310P

Страница 1: ...INSTALLATION AND MAINTENANCE INSTRUCTION FIGHTER 310P 230V MOS GB 0850 4 FIGHTER 310P 511350 L E K Fighter 310P Fighter 310P...

Страница 2: ...LEK LEK 1 2 LEK LEK 3 4 5...

Страница 3: ...ve offset 0 20 Heating curve offset 2 20 Setting using diagrams 20 Dealing with malfunctions Low temperature or a lack of hot water 21 Low or a lack of ventilation 21 Low room temperature 21 High room...

Страница 4: ...40 285 21 MARKARYD SWEDEN Maxiumum water supply pressure 16 bar Immersion heater R50 8000W 230 V Operating pressure tap water 6 bar Expansion vessel tap water charge pressure 3 5 bar Expansion vessel...

Страница 5: ...o that its temperature drops and the refrigerant changes state from gas to liquid The refrigerant then goes via filters to the expansion valve where the pressure and temperature are further reduced Th...

Страница 6: ...4 Upper visible part of the front panel Display screen Art nr 611603 2 1 bar 3 0 4 2 1 bar 3 0 4 2 1 bar 3 0 4 41 83 90 5 111 98 6 523 70 5 135 3 261 5 Switch Pressure gauge Indicator lamps Extra hot...

Страница 7: ...e Dealing with malfunctions Indications on the numerical display NOTE When switching from Standby mode to normal mode 1 the numerical display can remain dimmed for a brief period This can also occur a...

Страница 8: ...r hidden part of the front panel Art nr 611603 2 1 bar 3 0 4 2 1 bar 3 0 4 2 1 bar 3 0 4 111 98 6 523 Indicator lamps Heating curve selection Operating mode Channel selection I H J G L Miniature circu...

Страница 9: ...ions G Art nr 611822 Operating mode When the heat pump is started all functions immersion heater circulation pump and auto matic heating control system are running Pressing the Operating mode button o...

Страница 10: ...adjustment of basic settings Cold weather conditions If the room temperature is low increase the heating curve selection setting by one step If the room temperature is high reduce the heating curve se...

Страница 11: ...wners LEK The heat pump and its ventilation ducting require some regular maintenance when the following points should be checked The numbers in brackets refer to the section Compo nent locations Clean...

Страница 12: ...ion vessel normally 0 5 bar and 2 5 bar 25 mvp See Commissioning and adjusting Pressure gauge Extract air temperature Checking the safety valves L E K 2 1 bar 3 0 4 2 1 bar 3 0 4 FIGHTER 310P has thre...

Страница 13: ...between about 50 and 60 C The Extra hot water knob 18 on the front panel is used to increase the hot water capacity Temperatures in FIGHTER 310P NOTE Thetransport guard around the compressor mustberem...

Страница 14: ...es in the boiler section The pressure vessel in the FIGHTER 310P is approved for max 9 0 bar 0 9 MPa in the water heater and 2 5 bar 0 25 MPa in the double shell section Overflow water from the evapor...

Страница 15: ...o building regulation approval notify the Local Authority of intention to install Warning to the installer Use only manufacturer s recommended replacement parts Tap water connection Hot and cold water...

Страница 16: ...xhaust air devices it may be a good idea to install a silencer in the duct This is especially important if there are exhaust air devices in bedrooms Because the heat pump contains a flammable refriger...

Страница 17: ...front panel see under Service Open ing the front panel and moving certain cables as described under Electrical diagram Changing the output Connection Power rating as set at the factory Max current NO...

Страница 18: ...in defrosting mode In addition the flow temperature is limited to maxi mum 60 C Art nr 611 1 2 3 4 5 6 1 2 3 4 5 6 1 1 2 3 4 5 6 1 2 3 4 5 6 Immersion heater operation connec tion on delivery Limited...

Страница 19: ...V SKYDDSKLENSP NNING SELV B 1 2 3 4 5 6 7 8 B R R A B RUMSGIVARE RUNDSTYRNING UTEGIVARE B A Rundstyrning eller effektvakt 14 Rundstyrning RS och effektvakt EV Brytande kontaktfunktion RS EV EV RS SKYD...

Страница 20: ...ter screw to A Set the dimensioned capacity 35 on the circula tion pump 16 See the section Pipe connections Pump and pressure drop diagram Make sure that the switch is not in an intermediate position...

Страница 21: ...heating control system and Front panel The heating water can be drained off through drain valve 51 using an R15 1 2 hose coupling Remove the cover 80 from the valve Now screw on the hose coupling and...

Страница 22: ...2 V RMEKURVA 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1514 13 12 11 10 8 7 6 5 4 3 2 1 40 C UTETEMPERATUR 10 0 10 5 5 30 40 50 60 7...

Страница 23: ...witch 8 set to 0 MCB 7 tripped See the section Dealing with mal functions Resetting the miniature circuit break ers Tripped temperature limiter 6 Contact service Closed or throttled filler valve 46 on...

Страница 24: ...the fault code must be cleared from the display by switch ing the heat pump off and on again Middle lamp lit Defrosting When there is too much ice on the evaporator defrost ing takes place After this...

Страница 25: ...ault in the refrigerant circuit or its controller Request a service When the compressor is not operational the extract air temperature lies at about the same level as the room temperature High extract...

Страница 26: ...ide temperature Actual value 04 Evaporation temperature Actual value 05 Extract air temperature Actual value 06 Curve slope Heating curve selection 07 Offset Heating curve offset 08 Temperature compre...

Страница 27: ...ge 0 27 26 28 15 14 5 13 41 40 39 38 37 36 35 Re 1 Re 2 Re 3 Re 4 Re 5 Re 6 Re 7 29 230 V 12 V B1 C1 34 Brun Bl Svart VR1 C2 C3 F3 F1 F2 C4 L2 L1 5 2 1 3 4 P3 P1 P2 1 2 3 4 5 6 7 8 6 0 kW 1 Noll bleck...

Страница 28: ...31 32 94 1 88 86 30 37 Fram ledning radiatorer 11 9 59 16 17 44 70 19 44 89 78 27 36 33 58 95 52 96 97 8 62 48 63 87 65 99 14 82 ter ledning radiatorer k v v v 41 103 51 80 71 50 66 151 149 74 73 84 9...

Страница 29: ...atic heating control system and compressor 8 Switch positions 0 1 9 Terminal block power supply 10 Contactor step 1 11 Terminal block docking 13 Terminal block 14 Terminal block 15 Outdoor sensor 16 C...

Страница 30: ...d in front of the heat pump for servicing Measuring principle Kl mring Klemmring Cu r r Kupferrohr A B och Undvik r rdragning inom streckmarkerat omr de f r att underl tta service Skyddsklensp nning 1...

Страница 31: ...r Max pressure in double jacket volume 0 25 MPa 2 5 bar Breaking value high pressure pressostat 2 45 MPa 24 5 bar Breaking value low pressure pressostat 0 15 MPa 1 5 bar Design pressure in double jack...

Страница 32: ...cabinet 385 535 mm Part no 089 428 ROOM SENSOR RG 10 In some cases a room sensor can be used as a sup plement to the ordinary automatic control system LEK 2 1 3 4 5 6 7 8 9 Accessories LEK Heightening...

Страница 33: ...31 FIGHTER 310P...

Страница 34: ...FIGHTER 310P 32...

Страница 35: ......

Страница 36: ...Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk www volundvt dk NIBE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fax 05141 7546 99 E mail info nibe de www nibe de CH NIBE...

Отзывы: