Control conditions 

 

Max time hot water production (menu 1.7)

 indicates the proportion of the period 

time (menu 1.6) that hot water production is to prioritise over heat production. If the 
max time is as long as or greater than the period time, then hot water is always 
prioritised. If, on the other hand, the max time is set to 0, heat production is always 
prioritised. 
 

 

If a compressor triggers on ”High return temperature” during hot water 
charging, 

the compressor will not restart before the temperature on the hot water 

sensor has dropped to the specified start temperature (menu 1.1). This means that it is 
possible to run hot water charging to the return temperature, if required. At high return 
temperatures, the compressor stops, the three way valve shifts to radiator and the heat 
medium pump continues to run. 
 

 

At ”HP alarm” during hot water charging, 

the compressor stops and both the start 

and stop temperatures for the compressor drop 2 degrees. This is shown in the display 
in the menu for start and stop temperature as follows: ”48 (-2) °C”. To reset the drop 
to 0, press ”Enter” twice in any of the hot water menus. The alarm is automatically 
reset twice when the pressostat has returned and the high pressure alarm is given. 
However, the alarm is shown in the display for as long as the pressostat is deployed 
and the alarm remains in the alarm log. Maximum reduction of the start and stop 
temperatures is 4 degrees. If the stop temperature for compressor at XHW charging 
(menu 1.3) is greater than the stop temperature for HW (menu 1.2) and a high pressure 
alarm occurs during hot water charging, the XHW stop is forced to reduce to the same 
level as the HW stop. 

 
 

Program versions 

 

 

 
 

Miscellaneous 

 

 

 

 

Tips 

 

 

 

Document versions 

 

050112, document created, MS 

 

SIT 

GB

 

     0550-1

 

HOT WATER PRODUCTION 
M10384

 

SERVICE INSTRUCTIONS 

HOT WATER PRODUCTION 

FIGHTER 1320

 