The lower values in the
north of Sweden are due
to the lower design out-
door temperature.

Control

7

For Home Owners

FIGHTER 1210

Skellefteå

Umeå

Örnsköldsvik

Sundsvall

Hudiksvall

Gävle

Stockholm

Visby

Luleå

Jönköping

Göteborg

Borås

Halmstad

Markaryd

Helsingborg

Malmö

Växjö

Kalmar

Linköping

Norrköping

Karlskrona

Ystad

Simrishamn

Örebro

Karlstad

Hässleholm

Uppsala

Västerås

Söderhamn

11 (5)

10 (5)

9 (5)

9 (4)

8 (4)

8 (4)

9 (4)

Gällivare

Östersund

Kiruna

Falun

9 (5)

11 (5)

12 (6)

Example:

Map

When there is a demand for hot water, the heat pump
gives this priority and devotes its entire output to
water heating. No room heat is produced in this
mode. When the demand for hot water is high, the
maximum time for water heating is approximately 45
minutes. After this, room heating is produced for 15
minutes before further water heating can take place.

If the electrical module is connected for heat produc-
tion before hot water charging, one stage remains
operative during hot water operation. Hot water
charging starts when the hot water sensor has fallen
to the set start temperature (30 – 49 °C). In order to
reach the maximum hot water temperature, hot water
charging is stopped by the operating pressostat on
the heat pump. In addition, charging can take place
when the heat pump has reached its stop-level for
heating mode at the same time as less than 2 °C is
needed before the start of hot water. The purpose of
this is to minimise the number of starts.

NOTE!  The indicated hot water temperature is mea-
sured on the lower part of the water heater jacket.
This means that it is not the exact temperature of the
hot water. Usually the outgoing hot water is hotter
than the indicated temperature.

For occasional higher demand for hot water, the Extra
hot water function can be used to raise the tempera-
ture to about 60 °C for 24 hours (press the Extra HW
button once). The electrical module is used to raise
the temperature above 50 °C.

There is also a function for periodic raising of the hot
water temperature (press the Extra HW button twice).
In this mode, the temperature is raised temporarily by
means of the electrical module to about 60°C for a
period of between 1 and 90 days.

The supply of heat to the house is regulated in accor-
dance with the chosen setting of the regulating curve
(curveslope and offset). After adjustment, the correct
amount of heat for the outside temperature is sup-
plied. The heat pump’s flow temperature. (WW-out)
will hover around the theoretical required value (the
value in brackets on the display). For subnormal tem-
peratures the computer calculates a deficit in the form
of degree minutes, which results in the acceleration of
heat production. The larger the subnormal tempera-
ture, the greater the heat production.

There are four stages to heat production, one for the
heat pump and three for the electrical module. The
output of the electrical element as supplied is 
6 kW (FIGHTER 1210 – 4, 3 kW) but it can be rewired
to give 9 kW

To be able to produce heat when the collector circuit is
disconnected, or during servicing, the heat pump can
be set to standby mode, in which case heat is pro-
duced only by the immersion heater. Hot water is not
produced in standby mode. The compressor and col-
lector system are then shutoff and only the heat medi-
um circuit and the immersion heater are active. The
temperature is controlled by the thermostat (3). To
select standby mode, set the switch (8) to   

.

Heating

Hot water

Standby mode

Содержание Fighter 1210

Страница 1: ...R INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER 1210 MOS GB 0428 1 411195 FIGHTER 1210 LEK Fighter 1215...

Страница 2: ......

Страница 3: ...ffset 2 21 Heating curve offset 0 21 Heating curve offset 2 21 Component placement 4 kW Component placement 4 kW 22 Component placement 5 10 kW Component placement 5 10 kW 23 List of components List o...

Страница 4: ..._ _ _ _ _ FIGHTER 1210 _ _ kW Installation engineers Completedby the installer when the heat pump is installed The type of brine Mixing proportion freezing point Active drilling depth collector length...

Страница 5: ...ressed in the compressor The refrigerant the tem perature of which has now been raised is passed to the condenser where it gives off its energy to the heat ing medium circuit and if necessary to the w...

Страница 6: ...r Home Owners 4 Front panel Indicator lamps Function keys Display B Switch A D Increase reduce heat C E NOTE Make sure there is water in the heat pump before turning the switch A into position 1 or WW...

Страница 7: ...when additional heat is allowed Flashing rapidly when only additional heat is on Alarm Flashes rapidly when a fault has occurred Raise lower heat The Increase reduce heat knob raises or lowers the ro...

Страница 8: ...ve refer to a system where the flow temperature needs to be approximately 35 40 C resp 45 50 C on the coldest day The values stated on the map see the next page apply for the Curve slope The first val...

Страница 9: ...outgoing hot water is hotter than the indicated temperature For occasional higher demand for hot water the Extra hot water function can be used to raise the tempera ture to about 60 C for 24 hours pr...

Страница 10: ...r then appears within the brackets for HW start Press the Increase or Reduce button to select the start temperature for the hot water heating Press the Channel button to continue Outdoor Current outdo...

Страница 11: ...unning hours for heat pump Add time Shows the total hours of operation for addi tional heat Basic Change the left figure from 0 to 1 using the Increase button at the same time as pressing the Oper ati...

Страница 12: ...s back when being moved into a building Transport and storage Installation Guideline values for collectors Inspection of the installation FIGHTER 1210 For use with 40 x 2 4 PN 6 3 PEM hose For size 4...

Страница 13: ...ture calculated by the computer is obtained General Settings GM P Current value for number of degree minutes The value can be changed in order to hasten the start of heat production Setting range 3050...

Страница 14: ...ith EP Option 2 5 may not be used Select the right operating mode before Add drift is activated Add drift locks the operating mode function Man Manual test of outputs Change Man 0 to Man 1 or Man 2 to...

Страница 15: ...days at step 1 WW out Shows the flow temperature at step 1 FDP int 2 Shows the number of days at step 2 WW out Shows the flow temperature at step 2 It is possible to set the number of days from 1 to...

Страница 16: ...ircuit must be provided because of the risk of dirt and freezing in the evaporator This requires an additional heat exchanger Pipe installation must be carried out in accordance with current norms and...

Страница 17: ...ection of ambient cold possible To avoid condensation all pipes and other cold sur faces must be isolated with diffusion proof material Where the cooling demand is high fan convectors with drip trays...

Страница 18: ...h 1000 2 4 8 20 80 40 Tryckfall Fl de 1250 1500 1750 60 6 0 0 mvp kPa 250 500 750 0 l h 1000 2 4 8 20 80 40 Tryckfall Fl de 1250 1500 1750 2500 2250 2500 2250 2000 2000 60 6 FIGHTER 1215 4 FIGHTER 12...

Страница 19: ...t pump must not be connected without the permission of the electricity supplier and must be connected under the supervision of a qualified electrician If a miniature circuit breaker is used this shoul...

Страница 20: ...210 has an immersion heater which is connected for 6 kW on delivery FIGHTER 1210 4 3 kW immersion heater output The change over to oth er outputs is done by connecting cables in the electri cal module...

Страница 21: ...ck collector JK Soil collector VV Hot water Operating mode button F r ngare K ldb rarpump Kompressor Kondensor VV KV V rmeb rar pump Expansionsventil Kylmodul Elkassett V xelventil V rme retur Dubbelm...

Страница 22: ...rine pump menu Add driftin the service menu Set the Brine pump to position 1 and press Operating mode Set Add drift to 1 and press Operating mode Ensure the brine and heating medium pumps are vented a...

Страница 23: ...set is then set A suitable value for floor heating is 1 and for radiator systems 2 Offset heating curve 2 Setting using diagrams 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 3...

Страница 24: ...Component placement 4 kW 22 FIGHTER 1210 For the Installer 88 75 38 LEK 11 12 69 39 68 13 14 26 3 10 6 67 25 8 9 34 29 30 VB Fram 49 50 C Varmvatten 51 C LEK...

Страница 25: ...Component placement 5 10 kW 23 For the Installer FIGHTER 1210 75 88 38 LEK 9 68 39 26 97 25 3 6 8 67 10 29 30 36...

Страница 26: ...Component placement FIGHTER 1210 For the Installer 24 LEK 41 18 65 17 27 7 42 48 28 33 LEK 16 76 87 24 35 96 19 4 86 94 77 71 70 89 5 LEK 73 70 99 71 58 75 95 72 74...

Страница 27: ...Anode enamel 39 Reset motor protection 41 Low pressure pressostat 42 Service connection low pressure 48 Expansion valve 52 Safety valve collector side 58 Cover enamel 63 Particle filter KB R25 female...

Страница 28: ...Electrical diagram 4 kW FIGHTER 1210 For the Installer 26 Sheet 1 2 Compressor Relay card Connected output 3 kW on delivery Immersion heater...

Страница 29: ...agram 4 kW 27 For the Installer FIGHTER 1210 Sheet 2 2 Relay card Outside sensor Compressor start Immersion heater step 1 Immersion heater step 2 Brine pump Heating medium pump Reversing valve Compres...

Страница 30: ...Electrical diagram 5 10 kW FIGHTER 1210 For the Installer 28 Sheet 1 2 Compressor Relay card Connected output 3 kW on delivery Immersion heater...

Страница 31: ...diagram 5 10 kW 29 FIGHTER 1210 For the Installer Sheet 2 2 Relay card Outside sensor Compressor start Immersion heater step 1 Immersion heater step 2 Brine pump Heating medium pump Reversing valve So...

Страница 32: ...taller CPU unit 4 kW CPU unit 5 10 kW CPU card Low pressure Brine in Brine out Heat medium return Heat medium flow Operating pressostat Low pressure Brine in Brine out Heat medium return Heat medium f...

Страница 33: ...heat pump for servic ing An area of 800 mm is required in front of the FIGHTER 1210 for service work When FLM 30 is fitted on FIGHTER 1210 the distance to the wall should be 50 mm 598 179 525 525 30 3...

Страница 34: ...3 0 18 0 22 0 26 Max temp flow return circuit C 60 50 IP 21 Volume water heater litres 160 Starting current A 42 24 24 24 26 Fuse incl imm heater 6 kW A 16 16 16 20 20 Output brine pump W 130 130 170...

Страница 35: ...ur givare Outdoor temperature sensor Aussentemperatur f hler Artikel 018764 Outside sensor Part No 018 764 Particle filter Part No 424 043 R20 1 024 076 R25 1 Clips Part No 016 240 Enclosed kit 63 15...

Страница 36: ...reaker trips repeatedly call an electrician Cause Compressor and electric module do not heat Action Check and replace blown circuitand main fuses Cause The compressor does not run because of a too low...

Страница 37: ...rt up of cold installation Action Use Electric boiler mode Cause Bad circulation in collector system due to inferior venting low pressure or ice if ice has formed the brine pump 35 will be warm Action...

Страница 38: ...in the venting screw Start FIGHTER 1210 and check whether the circu lation pump runs It is usually easier to start the circulation pump with FIGHTER 1210 running switch 8 set to 1 If helping the circu...

Страница 39: ......