Nibe F2030 Скачать руководство пользователя страница 1

Installer manual

LEK

NIBE™ F2030

Air/water heat pump

IHB

 

GB

 

15

40

-

231115

Содержание F2030

Страница 1: ...Installer manual LEK NIBE F2030 Air water heat pump IHB GB 1540 4 231115...

Страница 2: ......

Страница 3: ...g and venting the heating medium sys tem 23 Balance temperature 23 Stop temperature 23 Soft starter 23 Compressor heater 23 Collar heater 23 Phase sequence control 24 Start up and inspection 24 Readju...

Страница 4: ...ccordance to applicable parts of the machinery directive 2006 42 EC Children should be supervised to ensure that they do not play with the appli ance This is an original instruction manual Translation...

Страница 5: ...ions and fire can occur Always use a fuse with the correct rating in the locations where fuses are to be used Connecting the unit with copper wire or other metal thread can cause unit breakdown and fi...

Страница 6: ...r supply immediately after operation has start Wait at least 5 minutes otherwise there is a risk of water leakage or breakdown Do not control the system with the main switch This can cause fire or wat...

Страница 7: ...llation data in the User manual Date Signature Notes Description System flushed System vented Particle filter Shut off and drain valve Charge flow set Fuses property Safety breaker Earth circuit break...

Страница 8: ...e du Pou du Ciel 01600 Reyrieux FR Tel 04 74 00 92 92 Fax 04 74 00 42 00 E mail info nibe fr www nibe fr NIBE Energy Systems Ltd 3C Broom Business Park Bridge Way Chesterfield S41 9QG GB Tel 0845 095...

Страница 9: ...the neighbours F2030 must not be placed so that recirculation of the outdoor air can occur This causes lower output and impaired efficiency The evaporator should be sheltered from direct wind which n...

Страница 10: ...s used to collect and lead away condensation water from the heat pump NOTE It is important to the heat pump function that condensation water is led away and that the drain for the condensation water r...

Страница 11: ...arv Vattenl s LEK APH Water seal Joint The condensation water is lead to an indoor drain subject to local rules and regulations Route the pipe downward from F2030 The condensation water pipe must have...

Страница 12: ...n avst nd vid anv ndning av flera F2030 600 mm 3000 mm 400 mm Minimalt fritt utrymme 600mm Minimalt fritt utrymme Minimum free space Free space behind Free space in front Minimum free space Minimum di...

Страница 13: ...Removing the side cover LEK APH 11 Chapter 2 Delivery and handling NIBE F2030...

Страница 14: ...1 EP2 BT17 BP2 AA101 QN1 QN31 WM5 QN30 QN34 GQ10 HS1 AA100 UB1 XL40 EB13 GQ1 EB11 QN2 XL20 EB10 BP10 RM1 APH BT16 EP1 UB1 XL40 PF3 XL2 BT3 XL1 BT12 BT28 PF1 PF3 NIBE F2030 Chapter 3 The heat pump desi...

Страница 15: ...T16 Temperature sensor suction gas BT17 Temperature sensor ambient BT28 Electrical components Joint card sensor AA100 Joint card AA101 Compressor heater EB10 Condensation water trough heater EB11 Coll...

Страница 16: ...3 Fan control board AA102 Phase sequence monitor 3 phase BA1 Fuse for external heating cable 250 mA F3 Automatic protection 10 A 30 mA FB1 Motor fuse FC2 Contactor main contactor fan QA51 Terminal blo...

Страница 17: ...lower connection XL2 on F2030 All outdoor pipes must be thermally insulated with at least 19mm thick pipe insulation Install shutoff and drain valves so that F2030 can be emptied in the event of prolo...

Страница 18: ...LiYY screened LiYCY Cable area at least 0 22with cable lengths less than 50m Alternatively the relevant screened signal cable is connected from terminal block X5 to the indoor module from NIBE The rou...

Страница 19: ...Accessibility electrical connection Removing the side cover Unscrew the screws and lift off the cover LEK APH 17 Chapter 5 Electrical connections NIBE F2030...

Страница 20: ...o high voltage cable when cable routing Power connection LEK APH Incoming supply Connection Incoming supply cable is supplied and factory connec ted to the terminal block X1 Approx 1 8 m cable is acce...

Страница 21: ...mp To let F2030 control the charge pump GP12 connect it to the terminal block X3 1 PE 3 L and 4 N Pump activity is dependent on the status of F2030 heat ing hot water requirement and the ambient tempe...

Страница 22: ...image 5 6 7 4 2 3 1 External F2030 X3 EB14 External heat cable F3 NOTE The pipe must be able to withstand the heat from the heating cable To ensure this function the accessory KVR 10 should be used C...

Страница 23: ...included in this time If the ambient temperature falls to a level below the set value stop temperature downtime in channel A7 compressor operations are blocked and all heating must take place using th...

Страница 24: ...ontact for external indication of common alarms The function becomes active with all types of existing alarms Max load on the relay con tact is250V 2A The connection for external indication of common...

Страница 25: ...below the set value for stop temperature heating must occur using the addi tional heat Soft starter F2030 is equipped with a soft start AA10 that limits the inrush current for the compressor Compress...

Страница 26: ...r 9 Restart any NIBE SMO or NIBE indoor module See information in relevant manual on www nibe eu 10 Once the connection is made the compressor starts after approx 180 minutes if needed 11 Adjust the c...

Страница 27: ...rees lower Quoted outputs refer to compressor fan and control at nominal heating medium flow During operation that requires defrosting the relationship between input and output is reduced by about 10...

Страница 28: ...can be adjusted and read off in the indoor module Navigation LP HP 34 15 88 90 86 41 33 89 93 34 91 Plus button The plus button S1 is used to browse through the channel system forwards or raise the v...

Страница 29: ...lways active when the compressor is switched off The condensation water trough heater is connected during defrosting when the ambient temperature falls below or is equal to 2 5 C If the collar heater...

Страница 30: ...at any point during the total 60 minutes falls below channel A7 2 1 C the counter is reset It does not start counting again un less the temperature is sufficiently high once again B Set temperature f...

Страница 31: ...outdoor air 3 When the temperature on the return line sensor channel T3 falls below 10 C 4 The high pressure switch deploys during defrost ing This is indicated as alarm 10 in channel S1 and the comp...

Страница 32: ...5 The temperature on the flow temperature sensor falls below 4 C NIBE F2030 Chapter 7 Control Introduction 30...

Страница 33: ...within 240 minutes it becomes continuous Low evaporation temperature Appears if 10 safety defrosts in a row have occurred 19 Value S2 Shows the compressor status Compressor off 00 Compressor on 01 Com...

Страница 34: ...heat is permitted The value is A6 adjustable between 1 and 120 minutes Factory setting 120 minutes Stop temperature the set outdoor air temperature value when the downtime relay is activated F2030 A7...

Страница 35: ...ettings on the control equipment Fuses have tripped Replace the fuse or reset the MCB Cold outdoor air Indicated as 03 in channel S1 Wait until the ambient temperature is 2 C higher than the heat pump...

Страница 36: ...ar heater in channel A14 Ice build up on the fan blades and front grille NOTE Only applies in certain areas Deicing fan channel A15 not activated Activate deicing fan in channel A15 Sensor placement B...

Страница 37: ...87 4 348 45 1 426 3 583 50 1 278 2 968 55 1 136 2 467 60 1 007 2 068 65 0 891 1 739 70 0 785 1 469 75 0 691 1 246 80 0 607 1 061 85 0 533 0 908 90 0 469 0 779 95 0 414 0 672 100 Data for hot gas senso...

Страница 38: ...3 25 3 82 15 13 20 3 58 11 88 15 3 33 9 392 10 3 07 7 481 5 2 80 6 000 0 2 54 4 844 5 2 28 3 935 10 2 03 3 217 15 1 80 2 644 20 1 59 2 186 25 1 39 1 817 30 1 22 1 518 35 1 07 1 274 40 0 93 1 075 45 0...

Страница 39: ...0 With integrated EMK 310 Part no 069 084 VVM320 Copper 3 x 400 V Part no 069 108 Stainless Steel 3 x 400 V Part no 069 109 Enamel 3 x 400 V With integrated EMK 300 Part no 069 110 Stainless Steel 3 x...

Страница 40: ...G1 28 mm Connection heating medium in to F2030 XL2 40 mm Connection drip tray drain XL40 400 mm Fritt utrymme bakom Fritt utrymme framf r Min avst nd vid anv ndning av flera F2030 600 mm 3000 mm 400 m...

Страница 41: ...bricks differences in ground level etc and should therefore only be seen as guide values F2030 works with low fan speed or high fan speed depending on the ambient temperature 2 m 6 m 10 m 9 7 51 58 5...

Страница 42: ...50 Hz Rated voltage 8 8 6 8 Arms Max operating current heat pump 6 3 4 3 Arms Max operating current compressor 23 5 19 2 Arms Starting current 41 68 48 68 W Nominal output fan low high 10 10 Arms Fus...

Страница 43: ...te Europe 3 3 9 5 3 3 7 SCOP 55 Average climate Europe 3 6 7 5 3 6 5 5 SCOP 35 Cold climate 3 1 8 3 1 6 SCOP 55 Cold climate 4 5 10 4 6 7 5 SCOP 35 Warm climate 3 9 11 5 3 9 8 5 SCOP 55 Warm climate 1...

Страница 44: ...temperature C C Outdoor air temperature 0 10 20 30 40 50 60 70 20 30 10 0 10 20 30 0 10 20 30 40 50 60 70 20 30 10 0 10 20 30 Supply temperature Return temp During shorter time it is allowed to have l...

Страница 45: ...ual energy consumption space heating warm cli mate 1 577 1 572 kWh Annual energy consumption water heating warm climate 142 120 142 122 Seasonal space heating energy efficiency cold climate 88 87 Wate...

Страница 46: ...COPd Tj 15 C if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TOL Min outdoor air temperature C 4 Tbiv Bivalent temperature COPcyc Cycling interval efficiency kW Pcych Cycling interval capacity C 65 WTOL M...

Страница 47: ...if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TOL Min outdoor air temperature C 5 1 Tbiv Bivalent temperature COPcyc Cycling interval efficiency kW Pcych Cycling interval capacity C 65 WTOL Max supply...

Страница 48: ...Electrical circuit diagram NIBE F2030 Chapter 11 Technical data 46...

Страница 49: ...47 Chapter 11 Technical data NIBE F2030...

Страница 50: ...NIBE F2030 Chapter 11 Technical data 48...

Страница 51: ...49 Chapter 11 Technical data NIBE F2030...

Страница 52: ...33 E Electrical cabinet 14 Electrical circuit diagram 46 Electrical connections 16 Charge pump 19 Connecting accessories 22 Connections 18 General 16 Optional connections 21 Power connection 18 Energ...

Страница 53: ...hnical Data 40 Technical Data 40 Temperature channels 31 The heat pump design 12 Component list electrical cabinet 14 Component location electrical cabinet 14 Component locations 12 List of components...

Страница 54: ......

Страница 55: ...ns Do not dispose of used products with normal household waste It must be disposed of at a special waste station or dealer who provides this type of service Improper disposal of the product by the use...

Страница 56: ...WS name Gemensamt WS version a74 working edition Publish date 2015 08 31 08 25 231115 NIBE AB Sweden Hannabadsv gen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu...