Nibe EMINENT-E 100 Скачать руководство пользователя страница 12

10

EMINENT-E 100

GB

Installation

Assembly

It is recommended that the water heater is installed in a 
room with an existing floor drain. The water heater can 
be installed vertically hanging on a flat wall (with down-
ward connections) or horizontally (with the rear down-
wards). 
Use the supplied hanging brackets (12) when hanging 
on a wall, these are secured first (Ø 8 – 10 mm screws), 
see the figure below. The water heater is then mounted 
on the bracket. The heater is now possible to shift to the 
sides a little bit, which makes pipe installation that much 
simpler.
For further fastening, the enclosed securing bracket (13) 
is fitted on the wall as a tip guard.
There must be a free area of 200 mm in front/under the 
water heater for service.
*A free area behind/above the EMINENT-E water heater 
is required for inspection of the sacrificial anode (40).  
See the section “Maintenance — Sacrificial anode”.

Pipe installation

The hot water heater is equipped with compression fit-
tings for copper or plastic pipes. Copper inserts should 
be fitted when a plastic pipe or annealed copper pipe is 
used.
All requisite valve fittings: shutoff/non-return valve, sa-
fety/drainage valve and mixing valve are factory fitted. 
An overflow pipe should be routed from the safety valve 
to an appropriate drain. The size of the overflow pipe 
should be the same as the safety valve’s (Ø 15 mm), the 
pipe should be routed so that water pockets do not oc-
cur, be designed to avoid frost and be well braced. 
In the event of uncertainty please contact a plumber or 
refer to applicable standards.
When the hot water heater is installed without a mixing 
valve, the thermostat setting must be such that the tap 
water temperature does not exceed 65 °C. Should a hig-
her temperature be required, follow applicable directions 
for the application.

Filling

The water heater must be filled with water before the 
mains supply is switched on. Filling takes place as fol-
lows:
 1 

 

Check that the venting screw (45) is tightened.

 2 

 

Check that the safety/drainage    

 

valve (23) is closed.

 3 

 

Open the shutoff valve by turning the knob (22) 
anticlockwise.

 4 

 

Vent the hot water heater by opening the hot 
water tap on the pipe system. When only water 
comes out of the tap this can be closed.

The water heater is now full and the power can be swit-
ched on.

Mixing valve setting

Turning the mixing valve knob (25) anticlockwise/clock-
wise increases/reduces the temperature of the tap wa-
ter. The setting range is between 50 – 65 °C.

Содержание EMINENT-E 100

Страница 1: ...0 EMINENT E 100 MONTERINGS OCH SK TSELANVISNING EMINENT E 100 SE INSTALLATION AND MAINTENANCE INSTRUCTIONS EMINENT E 100 GB ASENNUS JA HOITO OHJEET EMINENT E 100 FI Kontrollera att vatten finns i bere...

Страница 2: ......

Страница 3: ...gskoppling 15 mm 42 Blandvattenanslutning kl mringskoppling 15 mm 43 Anslutning s kerhets avtappningsventil kl mrings koppling 15 mm 45 Luftskruv f r lufttillf rsel vid t mning 95 Serienummerskylt MON...

Страница 4: ...s kerhets avtappningsventil och blandningsventil r monterad vid leverans Fr n s kerhetsventilen skall ett spillr r dras till l mpligt avlopp Spillr rets dimension skall vara samma som s kerhetsventile...

Страница 5: ...Om s dan varmvattenkran saknas eller vattenv rmaren monterats liggande m ste vattenv rmaren t mmas se avsnitt T mning 1 Bryt elstr mmen till vattenv rmaren 2 St ng avst ngnings backventilen genom att...

Страница 6: ...m ste anslutas till pos 43 IP 24 PED 97 23 EC Tekniska data tg rder vid driftst rning Kontrollera anl ggningens els kringar samt termostatens och blandningsventilens inst llningar Avvakta n gra timma...

Страница 7: ...mponenttien sijainti Komponenttiluettelo 1 Virtajohto maadoitetulla pistotulpalla 2 Muovikansi kytkent rasia 3 Muovikansi anodi 5 Termostaatti l mp tilanrajoitin 6 S hk vastus RAR 14 112 12 Ripustuska...

Страница 8: ...at venttiilit sulku takaiskuventtiili varo tyhjennysventtiili sek sekoitusventtiili on asennettu toi mitettaessa Varoventtiiliin on liitett v viem riin johdettu ylivuoto putki Ylivuotoputken halkaisij...

Страница 9: ...asentoon vedenl mmitin pit tyhjent katso kappale Tyhjennys 1 Katkaise vedenl mmittimen j nnitteensy tt 2 Sulje sulku takaiskuventtiili kiert m ll sen s t py r 22 my t p iv n niin pitk lle kuin mahdoll...

Страница 10: ...Tekniset tiedot Toimenpiteet toimintah iri iden yhteydess Tarkasta laitteiston varokkeet sek termostaatin ja sekoi tusventtiilin s d t Odota muutama tunti laskematta l mmint vett ja seu raa nouseeko...

Страница 11: ...compression tting 15 mm 42 Mixed water connection compression tting 15 mm 43 Connection safety drainage valve compression ring coupling 15 mm 45 Venting screw for air supply when draining 95 Serial nu...

Страница 12: ...alve sa fety drainage valve and mixing valve are factory tted An over ow pipe should be routed from the safety valve to an appropriate drain The size of the over ow pipe should be the same as the safe...

Страница 13: ...ction Emptying 1 Switch off the power to the water heater 2 Close the shutoff non return valve by turning the knob 22 clockwise until it bottoms 3 Open the hot water tap mentioned above 4 Remove the p...

Страница 14: ...used again NOTE The over ow pipe must be connected to pos 43 Technical speci cations Actions with operating disruptions Check the installation s fuses and the setting of the thermostat and mixing val...

Страница 15: ......

Страница 16: ...ideb k Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk www volundvt dk NIBE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fax 05141 7546 99 E mail info nibe de www nibe de C...

Отзывы: