GB
16
!
The minimum distance in front of
the stove opening to combustible
parts of the building or interior
decoration must be at least 1,2 m.
The dimension diagrams only
show the minimum permitted
installation distances for the
stove. When connecting to a steel
flue, also note the safety distance
requirements of the flue. The
safety distance between an un-
insulated flue and a combustible
part of the building should be at
least 450 mm.
Installation distances
WHEN INSTALLING TURNTABLE (OPTION)
the follow-
ing installation distances do not apply.
See the separate turntable installation instructions.
A = height from floor to chimney
connection upwards
B = height from floor to c/c chimney
connection rear
C = height from floor to air inlet
D = height from floor to lower edge
of hatch
A separate glass hearth
plate (accessory)
increases the connection
height to the chimney by
10 mm.
Permitted area for
combustible parts
of the building
* If the stove is placed on a hearth plate made of glass for example (accessory), the height from the floor is affected by a distance corresponding to the thickness of the hearth plate, for a free standing
glass hearth plate this is 10 mm.
** To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
INSTALLATION AGAINST COMBUSTIBLE WALLS
INSTALLATION AGAINST FIREWALLS
C610AG
1260
540
2100*
D 367
92
219
Combustible roof
140
110
B 1078*
A 1205*
C 389
40
495
Air inlet Ø67
Ø150
800
645
315
100
Combustible wall
650
730
595
265
50
650
Fire-retardant wall
of brick or concrete
1100
520
192
50
250**
900
Fire-retardant wall
of brick or concrete
800
528
600
600
242
100
Combustible wall
Содержание Contura C610AG
Страница 1: ...C610AG Style contura eu ...
Страница 9: ...34 2 1 3A 1 3A 2 ...
Страница 10: ...35 3B 3 3B 1 3B 2 ...
Страница 11: ...36 3B 4 3B 5 ...
Страница 12: ...37 4 5 6 ...
Страница 15: ...40 4 5 3 6 ...
Страница 16: ...811458 IAV SE EX C610AG Style 1 2021 10 27 NIBE AB Box 134 285 23 Markaryd Sweden contura eu ...