background image

6.

Press the 7-pole edge connector with zero number 0108
to 0112 on the relay card AA6 according to the image
below (NOTE! Be careful to match up the guide pin in
the edge connector with its hole in the card edge). Then
connect the loose wire ends as follows:

Blue cable with zero number 0108 to spring terminal
X6:6a.

-

Brown cables with zero number 0109 and 0110 to
spring terminal X6:3a.

-

Black cable with zero number 0111 to spring termi-
nal X6:1a.

-

Grey cable with zero number 0112 to spring terminal
X6:2a.

-

5

10

0108

0109

0110

0111

0112

AA6

X6

Kant-

kontakt

7

8

6

3

2

1

4

5

Edge

connector

HAHN 

LEK

LEK

Guide pin

7.

Connect the other individual wires as follows:

Brown cable with zero number 0101 to spring ter-
minal X6:3b.

-

Yellow/green cable with zero number 0107 to spare
connection on ground flat pin –PE2 (see image on
page 8) and in spring terminal X6:5a.

-

Brown cable with zero number 0104 to flat pin
AA7:38 and in spring terminal X6:4a.

-

Brown cable with zero number 0105 to flat pin
–AA7:40 and in spring terminal –X6:7a.

-

Black cable with zero number 0106 to flat pin
–AA7:42 and in spring terminal –X6:8a.

-

X6

7

8

6

3

2

1

4

5

0101

0104

0107

0105

0106

AA7

0102

0103

9

ACK 28

GB

Отзывы: