background image

© 

National Instruments Corp.

3

FP-DO-400

Figure 2.  

Basic Field Connections (Two Channels Shown)

Table 1 lists the terminal assignments for the signals of each 
channel.

Table 1.  

Terminal Assignments

Channel

Terminal Numbers

V

out

V

sup

COM

0

1

17

2, 18

1

3

19

4, 20

2

5

21

6, 22

3

7

23

8, 24

4

9

25

10, 26

5

11

27

12, 28

6

13

29

14, 30

7

15

31

16, 32

C

V

V

out

+

+

COM

a. Total Current Less

Than 5 Amps

Load

V

out

COM

Load

C

V

V

out

COM

b. Total Current Greater

Than 5 Amps

Load

V

out

V

sup

V

sup

COM

COM

COM

Load

Содержание FieldPoint FP-DO-400

Страница 1: ...r FieldPoint network module you are using with the FP DO 400 Features The FP DO 400 is a FieldPoint discrete output module with the following features Eight discrete output channels Sourcing outputs supply 2 A per channel 9 A2 per module Compatible with voltages from 5 to 30 VDC On Off LED indicators Hot plug and play operation 3 000 V input to output isolation Double insulated for 250 V safe work...

Страница 2: ...eld devices Although the external supply is not needed for the internal operation of the FP DO 400 the outputs source current from this external supply You may connect an external supply to power field devices by connecting to the V and C terminals of the terminal base Each channel has one output terminal Vout a common terminal COM internally connected to the C terminal and a supply terminal Vsup ...

Страница 3: ...nals of each channel Table 1 Terminal Assignments Channel Terminal Numbers Vout Vsup COM 0 1 17 2 18 1 3 19 4 20 2 5 21 6 22 3 7 23 8 24 4 9 25 10 26 5 11 27 12 28 6 13 29 14 30 7 15 31 16 32 C V Vout COM a Total Current Less Than 5 Amps Load Vout COM Load C V Vout COM b Total Current Greater Than 5 Amps Load Vout Vsup Vsup COM COM COM Load ...

Страница 4: ...er The result must be equal to or less than 9 A2 For example two channels with 2 A and one channel with 1 A 9 Α2 would be as follows 2 A 2 2 A 2 1 A 2 9 Α2 The outputs must not be short circuited to the potential of the C or COM terminals the negative voltage of the external supply Such a short circuit would cause many amps of current to flow through an output and would damage the output Check all...

Страница 5: ...d into a terminal base and power is applied the green POWER indicator turns on and the FP DO 400 informs the network module of its presence When the network module recognizes the FP DO 400 it sends initial configuration information to the FP DO 400 After receiving this initial information the green READY indicator turns on and the FP DO 400 is in its normal operating mode In addition to the green ...

Страница 6: ...s unless the product is specifically designed as the FP DO 400 is for such an application Even when a product like the FP DO 400 is used in applications with hazardous potentials follow these guidelines to ensure a safe total system The safety isolation of the FP DO 400 is from input to output not between channels on the same module If any of the channels on a module are wired at a hazardous poten...

Страница 7: ... 9 A2 For example 1 A on all eight channels or 2 A on two channels 5 V Voltage Range Output impedance 2 Ohms Maximum output current 0 67 A per channel 1 35 A2 per module Note Sum of output currents squared must be less than 1 35 A2 For example 0 4 A on all eight channels or 0 67 A on three channels Output delay times 50 µs Isolation 3 000 Vrms Safety isolation working voltage 250 Vrms designed per...

Страница 8: ...solation EN 61010 double insulation for 250 Vrms working isolation installation category II EMC directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 meters Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP DO 400 installed onto a terminal base Dimensions are given in inches millimeters Figure 5 Mechanical Dimensions 4 31 109 5 3 60 91 44 4 22 107 ...

Отзывы: