Alarms
79
TemBreak
PRO
P_SE-UM-001-EN
– V1.2.0
OAC (Optional Alarm Contact)
The OAC is an optional alarm which can be assigned with one of several types of alarms. When the assigned alarm is activated, the alarm will display on
the P_SE embedded display. The OAC also has a physical contact which closes with the activation of the OAC alarm. Refer to the
for
the list of available OAC alarm assignments.
The OAC is configurable by assigning it an alarm type (assignment), and the contact behaviour (reset mode), which can made using one or a combination of
the below methods:
-
TPED
-
TPCM
The physical contact mode is defined as either Auto-reset mode, or latching mode:
Auto-reset mode:
Contact will remain CLOSED for up to 500ms after the alarm deactivates, at which point it will OPEN automatically.
Latching mode:
Contact will remain CLOSED after the alarm deactivates, until the alarm is cleared via the P_SE embedded display or the TPED
where used.
TPED setting
TPCM setting
Default
“Assignment”
(Refer
Command ID: 117 “
Optional Alarm assignment setting
”
(Refer
PTA (Pre trip Alarm)
“Reset mode”
Automatic: Auto-reset mode
Latching:
Latching mode
Command ID: 116 “
Optional Alarm contact operation mode setting
”
Hex 00 00:
Auto-reset mode
Hex 00 01:
Latching mode
Auto-reset mode
Optional alarms List
ID
TPCM
holding register value (hex)
Custom Alarm Assignment
Remark
0
00 00
None
1
00 01
High OCR internal temperature
2
00 02
Neutral monitoring wire disconnection
3Ph+N Only
3
00 03
OCR self-test failure
4
00 04
Reserved
5
00 05
PTA (Pre trip alarm)
6
00 06
Custom Alarm 1
7
00 07
Custom Alarm 2
8
00 08
Custom Alarm 3
9
00 09
Custom Alarm 4
10
00 0A
Custom Alarm 5
11
00 0B
Custom Alarm 6
12
00 0C
Custom Alarm 7
13
00 0D
Custom Alarm 8
14
00 0E
Custom Alarm 9
15
00 0F
Custom Alarm 10
16
00 10
Custom Alarm 11
17
00 11
Custom Alarm 12
Notice
: The use of the OAC physical contact requires the connection of the OAC/PTA cable to the OAC port
located under the front cover of the P_SE MCCB. Refer to the
section for details on the
OAC/PTA cable.
Notice
: In the event that PTA (Pre trip alarm) is assigned to OAC, the contact operation mode is forced to auto-
reset mode, where the contact will OPEN up to 500ms after the PTA is no longer active.
Содержание Terasaki TemBreak PRO P SE Series
Страница 106: ...106 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex A Dimensions P160 Dimensions...
Страница 107: ...Annex A Dimensions 107 TemBreak PRO P_SE UM 001 EN V1 2 0 P250 Dimensions...
Страница 108: ...Annex A Dimensions 108 TemBreak PRO P_SE UM 001 EN V1 2 0 P400 Dimensions...
Страница 109: ...Annex A Dimensions 109 TemBreak PRO P_SE UM 001 EN V1 2 0 P630 Dimensions...
Страница 111: ...111 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex C I2t Let Through Curves P160_SE...
Страница 112: ...Annex C I2t Let Through Curves 112 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Страница 113: ...Annex C I2t Let Through Curves 113 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Страница 114: ...Annex C I2t Let Through Curves 114 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Страница 115: ...115 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex D Peak Let Through Curves P160_SE...
Страница 116: ...116 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Страница 117: ...117 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Страница 118: ...118 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Страница 121: ...121 TemBreak PRO P_SE UM 001 EN V1 2 0 This page is intentionally left blank...