Connections and User interface 

 

1

Modbus over USB

: used to connect a device running 

POWERMASTER

 or custom 

user application. Firmware update is also possible.  

2

DC Output:

 connected to the load. The output voltage is adjustable between 5 to 

55Vdc.  

3

DC-OK dry contact:

 normally open relay contact is available; the relay closes 

when the output voltage is >90% of the programmed output voltage value.  

4

DC Input:

 input voltage supply, range is from 12 to 48Vdc.  

5

Display:

 2-digits LED display used to program the device and read its status.  

6 Control keys:

 3 push buttons are provided to navigate through menus and to 

select various functions.  

Input Connection: 

 

 

+ = Positive DC 

 

- = Negative DC 

 

I

 = Earth ground 

 

Output Connection: 

 

 

+ = Positive DC 

 

- = Negative DC 

 

Auxiliary Connection: 
 
DC OK

: Dry contact 

 

NO 

 

COM 

 

Mini USB-B Type 

 

 

1 = VBUS (+5V) 

 

2 = Data (D-) 

 

3 = Data (D+) 

 

4 = Not connected (ID) 

 

5 = GND 

 

Recommended connecting cable 

(Fig.5) 

 

Recommended Tightening torque 

 
0.5-0.6Nm 
4.42-5.30 lbf in 

 

 

 

Input / output connections 

Solid: 2.5mm² / 12AWG 
Stranded:2.5mm² / 12AWG 
L: 6.0-7.5mm / 0.24-0.30in 

 
Input connection

 

DC Line 

 

 

 

 

Dimensions 

Distances 

(Fig.3)

 

 

 

Dimension 


mm 

40.0 

110.0 
115.0 

Distance 


 

mm

 

20 
50 

 

 

INSTRUCTIONS 

1) Description: 

 NDW240 can be supplied with any voltage between 11Vdc and 55Vdc, 

please respect the polarity

. The output voltage can be programmed to any 

voltage between 5Vdc and 55Vdc. 

To prevent damage in case of reverse polarity, the device is protected by an internal not replaceable fuse.   

NDW240 can be used in SELV and PELV circuits. 

2) Installation:

 use DIN-rails according to EN 60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point 

where the device is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).  
The device is provided with a thermal protection, a limited air flow can cause the thermal protection tripping. 
The device automatically restarts after cooling.  
To get normal operation reduce the temperature of the air surrounding the unit, increase the ventilation or reduce the load. 
 