3
Connections
Dimensions
Distances
(Fig.3)
1.
Input/Output
: double IO connection
(paralleled)
2.
FUSE:
30A/32V ATA blade user
replaceable
Input/Output Connection:
+ = Positive DC
- = Negative DC
Dimension
W
H
D
mm
80.0
120.0
100.0
Distance
A
B
mm
20
20
Mounting / Dismounting Instructions
(Fig.4)
For DIN rail mounting according to IEC 60715 TH35-7.5(-15). Mounting as shown in figure, with input terminals on lower side, with suitable cooling and maintaining a proper distance between
adjacent devices as specified in the User manual.
Mounting
1.
Tilt the unit slightly backwards.
2.
Fit the unit over the top edge of the rail.
3.
Slide it downward until it hits the stop.
4.
Press against the bottom for locking.
1
2
3
4
Dismounting
1.
Pull down the slide clamp lever.
2.
Tilt the unit upward.
3.
Unhook the unit from the rail.
1 & 2
3
Recommended connecting cable
(Fig.5)
Recommended Tightening torque
0.5-0.6Nm
4.42-5.30 lbf in
Input / output connections
Solid: 2.5mm² / 12AWG
Stranded:2.5mm² / 12AWG
L: 6.0-7.5mm / 0.24-0.30in
Содержание NCP12
Страница 4: ...4 NOTES ...