background image

TRACE

MATE

Chapter 4

Operation

4.1

Alarms

When an alarm condition occurs, the form c dry alarm
contact reacts and the corresponding alarm LED comes
on to indicate the cause of the alarm. Fault diagnosis for
these alarms is listed below.
RTD Fail: If the RTD sensor is not connected or
shorted, RTD FAIL alarm LED will turn on. Check that
the RTD sensor is properly connected. This alarm is not
latched and will be reset as soon as the RTD is properly
connected. In the event of an RTD failure, the heater
output is turned off to prevent a runaway heating
situation.
Low Temperature: Once the actual temperature is below
the low temperature alarm setpoint, LO TEMP alarm
LED will turn on. This will normally indicate that the
heater circuit is not providing enough heat to maintain the
setpoint. When a system is first turned on this alarm may
be activated. It is particularly useful in taking corrective
action in freeze protection systems to prevent a burst
pipe. This alarm is not latched and will be reset as soon as
the alarm condition disappears.
High Temperature: Once the actual temperature is above
the high temperature alarm setpoint, HI TEMP alarm
LED will turn on. This alarm is not latched and will be
reset as soon as the alarm condition disappears.
Current Fail: This alarm is activated when the TraceMate
control calls for heat and a heater current less than the
current fail alarm setpoint flows. Either the continuity of
the wiring and heat tracing cable is defective or a very
small heater is being switched. In order to detect faults on
dormant systems with the TraceCheck feature, which
turns on the heaters for several seconds every 24 hours,
this alarm is latched. Thus, once the condition is detected,
the alarm will remain on until it is reset.
Ground Fault Trip: This alarm is activated when the
ground fault current is above the ground fault trip alarm
setpoint. A ground fault is a current to ground caused by
moisture, corrosion or insulation breakdown. Often the
amount of ground fault current is not enough to trip the
heater circuit breaker but could result in a serious fire
hazard, especially with self-regulating cable.
When a ground fault is detected, the heater will be
switched off, even if the control is calling for heat. This
eliminates the need for an expensive ground fault circuit
breaker. Large ground fault currents will trip the heater
circuit breaker, so an intentional time delay is allowed for
the breaker to clear high fault currents, which can occur
on solidly grounded systems.
Since the heater may be shut off after a ground fault, it is
very important that the alarm outputs be used so
corrective action can be taken quickly enough to prevent
a process shutdown due to the loss of heat to a pipe.
Ground fault detection only works with resistance or

solidly grounded systems. If the system is ungrounded, it
must be grounded or an artificial ground must be created
by means of a zip-zag transformer. Once a ground fault
condition is detected, it remains latched until it is reset.

Status Indicators

Power On Indicator: When incoming voltage is applied
to the TraceMate, the green PWR ON indicator LED
should be on. If this LED is not on, check that the
appropriate voltage is present by connecting a meter
across terminals 1 and 2. If voltage is present and the
LED is off, the controller should be replaced and sent to
the factory for service.
Heater On Indicator: Whenever the heater is on, the green
HTR ON indicator LED will be on. This is useful for
checking correct operation of the control. If the ground
fault alarm light or RTD fail alarm light is on, the heater
will not switch on even if the actual temperature is below
the setpoint.

Alarm Reset

The low/high temperature and RTD fail alarms reset as
soon as the condition disappears. The ground fault trip
and current fail alarm are latched alarms. A latched alarm
will remain even if the alarm condition disappears. To
reset the latched alarms, remove incoming power for a
few seconds by opening and reclosing the circuit breaker.
Provided the alarm conditions are no longer present, the
alarms should all be reset when power is re-applied to the
TraceMate. It is also possible to reset the latched alarms
by momentarily switching S11 towards its ON position (
refer to Figure 2.1 ) even if the TraceMate is at control
with power applied.

Heater Setpoint and Alarm Setpoints

As stated in chapter 2, five setpoints can be adjusted by
properly setting up S1-9 and JP1 ( refer to Figure 2.1 ).
S1-9 consisits of 9 switches. They are S1, S2, S3, S4, S5,
S6, S7, S8 and S9. These 9 switches generate a Setpoint
Number in a range of 0-511. The exact value of this
Setpoint Number equals the sum of the contributions by
each switch. If a switch is in ON position, its contribution
to the Setpoint Number equals its labelled value on the
board. Otherwise, its contribution is zero. For example, if
all 9 switches are in ON position, Setpoint Number =
1+2+4+8+16+32+64+128+256 = 511. If only switches
S3 and S5 are in ON position, Setpoint Number =
0+0+4+0+16+0+0+0+0 = 20.
Depending on the jumper position of JP1, the Setpoint
Number generated by S1-9 can be interpreted as either
heater setpoint, or low temperature alarm setpoint, or high
temperature alarm setpoint, or ground fault trip alarm
setpoint, or current fail alarm setpoint.

Содержание tracemate

Страница 1: ...TRACEMATE OPERATOR S MANUAL ELECTRONIC THERMOSTAT ...

Страница 2: ...Conduit and Cabling 2 3 Power Wiring 2 3 Heater Wiring 2 3 Ground Connection 2 3 RTD Sensor Wiring 2 3 Alarm Wiring 2 4 3 Applications 3 1 Mechanical Thermostat Replacement 3 1 Alarm Annunciator 3 1 Switching Requirements 3 1 4 Operation 4 1 Alarms 4 1 Status Indicators 4 1 Alarm Reset 4 1 Heater Setpoint and Alarm Setpoints 4 1 5 Testing 5 1 Troubleshooting System Integrity 5 1 Calibration 5 1 Gr...

Страница 3: ... factory default values are Heater setpoint 20 C Low temp alarm 5 C High temp alarm 100 C Current fail alarm 0 3 A Ground fault trip alarm 30 mA Using This Manual Detailed information relating to switch and output ratings accuracy etc are detailed in Chapter 1 Product Overview Chapter 2 Installation discusses important mounting and wiring issues for reliable operation Chapter 4 Operation describes...

Страница 4: ...nments User Definable Options Heater Setpoint Low Temperature Alarm Setpoint High Temperature Alarm Setpoint 0 C 511 C 1 C steps 0 F 511 F 1 F steps Temperature Units 0 C or F Current Fail Alarm Setpoint 0 0A 30 0A 1 A steps Ground Fault Trip Alarm Setpoint 0mA 511mA 1 mA steps Enclosure Type E5 Nema 4X steel painted black Size Single pole 8 Hx6 Wx4 D Dual pole 10 Hx8 Wx4 D Features Quick release ...

Страница 5: ...GF Setpoint Number generated by S1 9 is interpreted as ground fault trip alarm setpoint in mA AMP Setpoint Number generated by S1 9 is divided by 10 and interpreted as current fail alarm setpoint in A SP Setpoint Number generated by S1 9 is interpreted as heater setpoint in C or F NONE Setpoint Number generated by S1 9 has no effects on any setpoints Warning The ground fault trip function is inten...

Страница 6: ...2 2 TRACEMATE Chapter 2 Installation Figure 2 1 TraceMate Controls and Indicators Figure 2 2 Typical Wiring Diagram ...

Страница 7: ...upply voltage must be 120VAC for TM 1SIH1 E5 RTD Single pole or 208 240VAC for TM 1DIH2 E5 RTD Dual pole and rated voltage range of the heat trace cable Wiring methods must conform to Class 1 Division II or Class 1 Zone II requirements Heater Wiring Connect heating cable wiring to terminals 3 and 4 See Figure 2 2 If the heating cable has a braid it should be terminated tothe ground stud using a ri...

Страница 8: ...te has a form c dry alarm contact and an active alarm output for driving an LED alarm indicator The alarm LED output is configured to turn on the alarm indicator when there is no alarm Refer to Figure 2 2 for contact and alarm output terminals The form c dry alarm contact is rated 0 5A 277Vac 0 1A 30Vdc The alarm LED output is rated 6Vdc 50mA It can drive a 6Vdc LED indicator These alarm contact a...

Страница 9: ...blem Alarm Annunciator If an alarm annunciator or programmable controller is available terminal 10 11 12 can be used as a low cost digital interface These terminals are form C dry con tacts A separate voltage source must be connected across these terminals as shown in Figure 3 2 for the annuncia tor to sense the alarm logic Switching Requirements Two different TraceMate models are available to acc...

Страница 10: ...off after a ground fault it is very important that the alarm outputs be used so corrective action can be taken quickly enough to prevent a process shutdown due to the loss of heat to a pipe Ground fault detection only works with resistance or solidly grounded systems If the system is ungrounded it must be grounded or an artificial ground must be created by means of a zip zag transformer Once a gro...

Страница 11: ...1 9 is interpreted as the high temperature alarm setpoint in C or F The factory default value is 100 C Ground Fault Trip Alarm Setpoint If the jumper on JP1 is at GF position the Setpoint Number generated by S1 9 is interpreted as the ground fault trip alarm setpoint in mA The factory default value is 30 mA Current Fail Alarm Setpoint If the jumper on JP1 is at AMP position the Setpoint Number gen...

Страница 12: ...ified by adjusting the heater setpoint dip switch 2 C above and below a known temperature on the RTD input to see if the heater turns on and off For example if the RTD input temperature is 25 C setting the heater setpoint to 27 C will force the heater on and conversely a 23 C setpoint will force the heater off By substituting a known resistor value for the RTD sensor and looking up the equivalent ...

Страница 13: ...which will be seen by the ground fault sensor as a ground fault Size the resistor according to the Heater Voltage 110 240 208 AC Volts Resistance 2700 6200 5100 Ohms Wattage 5 10 10 Watts Voltage Rating 250 500 500 DC Volts table to ensure sufficient ground fault current of 30mA 25 4 Apply power The ground fault indicator should come on after a short delay It should not be possible to turn on the ...

Страница 14: ...OVIDED FOR IN WRITING IN THIS WAR RANTY EACH CONTROL IS PROVIDED WITHOUT ANY WARRANTY OF ANY KIND EITHER EXPRESSED OR IMPLIED IN PARTICULAR WITH OUT LIMITING THE GENERALITY OF THE FOREGOING THE FOLLOW ING IMPLIED WARRANTIES AND CONDITIONS ARE EXPRESSLY DIS CLAIMED a ANY IMPLIED WARRANTY OR CONDITION THAT THE CON TROL WILL MEET YOUR REQUIREMENTS b ANY IMPLIED WARRANTY OR CONDITION THAT THE OP ERATI...

Страница 15: ...TRACEMATE ELECTRONIC THERMOSTAT P N 1501 0012_1 TMII 02 09 Printed in Canada Nextron Limited 6120 11th Street S E Calgary Alberta T2H 2L7 Tel 403 735 9555 Fax 403 735 9559 ...

Отзывы: