4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table 
below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 

mains.   

The AC input is connected 
to the UPS output. 

Plug  AC  input  power  cord 
to AC input correctly.   

The icon 

and the warning 

code 

  flashing on LCD 

display and alarm is sounding 

every second. 

EPO function is activated.  Set  the  circuit  in  close 

position  to  disable  EPO 
function. 

The icon 

and 

  flashing 

on LCD display and alarm is 
sounding every second. 

Line and neutral 
conductors of UPS input 
are reversed. 

Rotate mains power socket 
by  180°  and  then  connect 
to UPS system. 

The icon

  and 

flashing 

on LCD display and alarm is 

sounding every second. 

The external or internal 

battery is incorrectly 
connected. 

Check  if  all  batteries  are 

connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

Battery voltage is too high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The icon 

  and the icon 

 

are flashing on LCD 

display and alarm is sounding 
twice every second. 

UPS is overload   

Remove excess loads from 
UPS output. 

Fault code is shown as 43 and The 

icon 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 

automatically because of 
overload at the UPS 
output. 

Remove excess loads from 

UPS output and restart it. 

Fault code is shown as 14 and 
alarm is continuously sounding. 

The UPS shut down 
automatically because 
short circuit occurs on the 
UPS output. 

Check output wiring and if 
connected  devices  are  in 
short circuit status. 

Содержание MANTIS 1100 RT

Страница 1: ...www nextups eu Line Interactive Sinewave UPS MANTIS 1100 RT MANTIS 1500 RT MANTIS 2000 RT MANTIS 3000 RT Uninterruptible Power Supply System User Manual...

Страница 2: ...Rear Panel View 4 2 2 Install The UPS 4 2 3 Setup The UPS 5 2 4 Battery Replacement 7 2 5 Battery Kit Assembly option 8 3 Operations 10 3 1 Button Operation 10 3 2 LCD Panel 10 3 4 LCD Display Wordin...

Страница 3: ...trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an ea...

Страница 4: ...persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals...

Страница 5: ...4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communication port 9 SNMP intelligent slot 10 External batte...

Страница 6: ...l devices by setting shorter backup time for non critical devices Step 3 Communication connection Communication ports USB port RS 232 port Intelligent slot To allow for unattended UPS shutdown start u...

Страница 7: ...ted external battery boxes up to 4 units Step 7 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hou...

Страница 8: ...s and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the batte...

Страница 9: ...rt Step 3 Put assembled battery packs on one side of plastic shells and insert one more defect battery on the space Step 4 Cover the other side of plastic shell as below chart Then battery kit is asse...

Страница 10: ...dhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart...

Страница 11: ...TER Button Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS Confirm selection key Press this button to confirm selection in UPS setting mode SELECT Button Switch LCD...

Страница 12: ...information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited UPS status Indicates that programmable management outlets...

Страница 13: ...e outlets setting LCD display direction and exit 01 Output voltage setting Interface Setting For 208 220 230 240 VAC models you may choose the following output voltage 208 presents output voltage is 2...

Страница 14: ...for setting programmable outlet Step 1 Before entering setting mode the UPS should be in Stand by mode off charging and make sure the battery is connected The LCD display is shown as right Step 2 Pres...

Страница 15: ...iption LCD display ECO mode When the input voltage is within voltage regulated range UPS will power the output directly from the mains ECO is an abbreviation of Efficiency Corrective Optimizer In this...

Страница 16: ...too low 28 Inverter soft start fail 11 x Over temperature 41 x Inverter voltage high 12 x Over load 43 Inverter voltage Low 13 x 3 8 Warning Indicator Warning Icon flashing Alarm Low Battery Sounding...

Страница 17: ...y second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously...

Страница 18: ...tery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batte...

Страница 19: ...t your dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage...

Страница 20: ...V 9 Ah x4 12 V 9 Ah x6 Charging Voltage 27 4 VDC 1 54 8 VDC 1 82 1 VDC 1 Recharge Time 4 hours recover to 90 capacity PROTECTION Full Protection Overload short discharge and overcharge protection ALAR...

Отзывы: