PLATINUM Series Controllers User’s Guide
50
Reference Section: Programming Mode (PRoG)
7.4.1
Output Channel Mode (PRoG > oUt1
–
oUt6 > ModE)
Select Output Channel Mode (ModE) to configure the specified output.
Navigate to the desired setting. Settings include the following:
oFF
– Turn off the output channel (factory default)
PId
– Set the output to Proportional-Integral-Derivative (PID) Control Mode
oN.oF – Set the output to On/Off Control Mode
ALM.1 – Set the output to be an Alarm using the ALM.1 configuration
ALM.2 – Set the output to be an Alarm using the ALM.2 configuration
RtRN – Set up the output for Retransmission
RE.oN – Turn on the output during Ramp events
SE.oN – Turn on the output during Soak events
Select the indicated setting.
7.4.1.1
Turn Off Output Channel (PRoG > oUt1
–
oUt6 >
ModE > oFF)
Turn off this output (oFF).
7.4.1.2
PID Control Mode (PRoG > oUt1
–
oUt6 > ModE >
PId)
Select PID Control Mode (PId) for this output (factory default). PID parameters are
set outside the specific output submenus, as more than one output can be used for
PID control at a time. See
7.5 PID Configuration (PRoG > PID)
7.4.1.3
On/Off Control Mode (PRoG > oUt1
–
oUt6 >
ModE > oN.oF)
Select On/Off Control Mode (oN.oF) for this output. More than one output can be
set up for oN.oF control. For Heat / Cool control set the output connected to the
heater with ACtN equal to RVRS and the output connected to the cooling device
with ACtN set to dRCt.
Navigate to the desired setting. Settings include the following:
ACtN – Determines the action direction for control
dEAd – Sets the deadband value; the deadband value is applied in the
same units as the process variable to one side of Setpoint as determined by
the ActN direction
S.PNt – Allows either Setpoint 1 or Setpoint 2 to be specified as the
target value; Setpoint 2 can be set to track Setpoint 1 using the deviation
(dEVI) option (
)—a useful feature when setting
up for heat/cool operation
Select the indicated setting.