background image

Panel Mounting Instruction:

1.

Using the dimensions from the panel cutout diagram 
shown above, cut an opening in the panel.

2. 

Remove sleeve from the rear of the case by removing 
thumbnuts.

3.

Insert the unit into the opening from the front of the
panel, so the gasket seals between the bezel and the
front of the panel.

4.

Slip the sleeve over the rear of the case.

5.

Tighten the thumbnuts to hold the meter firmly in the panel.

Disassembly Instruction:

If necessary, the meter may be removed from the panel and
opened.

Warning: Disconnect all ac power from the unit
before proceeding.

1.

Remove all wiring connections from the rear of the 
instrument, by unplugging the power and input connectors.

2.

Remove both thumbnuts and set aside.

3.

Remove the sleeve and set aside.

4.

Remove the meter from the panel and bend the side 
panel detents on the case outward to release the board. 
Pull the board assembly out of the case.

WIRING

Wire the instrument according to the schematic below.

Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow all
instructions and warnings may result in injury!

This Quick Start Reference provides information 
on setting up your instrument for basic operation.
The latest complete Communication and
Operational Manual as well as free Software and
ActiveX Controls are available at

www.newportUS.com/i or on the CD-ROM
enclosed with your shipment

.

SAFETY CONSIDERATION

This device is marked with the international
Caution symbol.

The Controller is a panel mount device protected in
accordance with Class II of IEC 1010. Remember that the
controller has no power-on switch. Building installation
should include a switch or circuit-breaker that must be
compliant to IEC 947-1 and 947-3.

SAFETY:

• Do not exceed voltage rating on the label located on 

the top of the instrument housing.

• Always disconnect power before changing signal and 

power connection.

• Do not use this instrument on a work bench without 

its case for safety reasons.

• Do not operate this instrument in flammable or 

explosive atmospheres.

• Do not expose this instrument to rain or moisture.

EMC:

• Whenever EMC is an issue, always use shielded cables. 
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the 

instrument if EMC problems persist. 

MOUNTING

START HERE

Connect the main power connections in the figure shown
below.

FUSE

Connector Output Type For 115Vac  For 230Vac

DC

FUSE 1

Output 1

Relay

3 A(T)

3 A(T)

FUSE 2

Output 2 

Relay 

3 A(T) 

3 A(T) 

-

FUSE 3

Power 

N/A

100 mA(T)  100 mA(T)  100 mA(T)

FUSE 4

Power

N/A

N/A

N/A

400 mA(T)

CONFIGURATION

Button Functions in Configuration Mode

• To enter the Menu, the user must first press 

a

button.

• Use this button to advance/navigate to the next

menu item. The user can navigate through all the
top level menus by pressing 

a

.

• While a parameter is being modified, press this

button to escape without saving the parameter.

• Press the up 

b

button to scroll through “flashing”

selections. When a numerical value is displayed
press this key to increase value of a parameter that
is currently being modified.

• Holding the 

b

button down for approximately 

3 seconds will speed up the rate at which the set
point value is incremented.  

• In the Run Mode pressing 

b

causes the display to

flash the PEAK value – press again to return to the
Run Mode.

• Press the down 

c

button to go back to a previous

Top Level Menu item. 

• Press this button 

twice to reset the controller

to

the Run Mode. 

• When a numerical value is flashing (except set point

value) press this button to scroll digits from left to
right allowing the user to select the desired digit to
modify.

• When a set point value is displayed press this button

to decrease value of a set point that is currently being
modified. Holding the 

c

button down for

approximately 3 seconds will speed up the rate at
which the setpoint value is decremented.

• In the Run Mode pressing 

c

causes the display to

flash the Valley value - press again to return to the
Run Mode.

• Press this button to access the submenus from a

Top Level Menu item. 

• Press this button to store a submenu selection or

after entering a value — the display will flash a

STRD

message to confirm your selection.

• Press this button to reset flashing PEAK value.
• In the Run Mode, press ENTER twice to enable

Standby Mode with flashing 

STBY

- press again to

return to the Run Mode.

a

d

c

b

(UP) 

MENU

(DOWN)

ENTER

Reset: Except for Alarms, modifying any settings of
the menu configuration will reset the controller prior
to resuming Run Mode.

DISPLAY ABBREVIATIONS

SP1

Set Point 1 Value

SP2

Set Point 2 Value

CNFG

Configuration Menu

INPt

Input Type Menu

t.c

Thermocouple Input

k. . .J

Thermocouple Type

Rtd

RTD Input

385.2

RTD Curve and 

100 _

100 _/500 _/1000 _

. . . .

Connection Type

. . . .

RTD Sensor

392.4

(2, 3, 4-Wire)

1000

PROC

Process Input

0 - 0.1

100 mV Input Voltage

0 - 1.0

1 V Input Voltage

0 - 20

20 mA Input Current

0 - 10

10 V Input Voltage

RdG

Reading Configuration

dEC

Decimal Point

F.FFF.

Decimal Point

FLtR

Filter Constant

..FFFF

Position

0001..

Filter Constant Value

IN.Rd

Input/Reading Scale

..0128

and Offset Menu

IN 1

Input 1

IN 2

Input 2

Rd 1

Reading 1

Rd 2

Reading 2

ALR1

Alarm 1 Menu

AbSo

Absolute Mode

_dEV

Deviation Mode

LtcH

Latched Mode

UNLt

Unlatched Mode

Ct.CL

Contact Closure 

N.o.

Normally Open

N.c

.

Normally Closed

ActV

Active Type

AboV

Active Above

bELo

Active Below

Hi.Lo

Above High/Below
Low 

bANd

Above or Below Band

A.P.oN

Alarm Enable/Disable
at Power On

ALR.L

Alarm Low Value

ALR.H

Alarm High Value

ALR.2

Alarm 2 Menu

LOOP

Loop Break Menu

b.tIM

Loop Break Time

R.AdJ

Reading Adjust

SP.dN

Set Point Deviation

OUt1

Output 1 Menu

SELF

Manual Control

ººLO

Percent Low 

ººHI

Percent High

CtRL

Control Type

ON.OF

On/Off Control

4 - 20

Amplitude Control

PId

PID Control

ActN

Action Type

RVRS

Reverse Action

dRct

Direct Action

ANt1

Anti Integral

AUto

Auto PID 

A.tUN

Auto Tune PID

StRt

Start Auto Tune PID

PRoP

Proportional Band

RESt

Reset Setup 

RAtE

Rate Setup

CYCL

Cycle Time 

dPNG

Damping Factor

dEAd

Dead Band

ANLG

Analog Output

VoLt

Voltage Output

CURR

Current Output

Out.1

Output 1

Rd 1

Reading 1

Out.2

Output 2

Rd 2

Reading 2

RAMP

Ramp Time

SOAk

Soak Time

Id

ID Code Menu

CH.Id

Change ID Code

FULL

Full ID

SP.Id

Set Point ID

COMM

Communication Option*

NONE

Communication is
Not Installed

COLR

Display Color Selection

N.CLR

Normal Color
Display

1.CLR

Alarm 1 Color Display

2.CLR

Alarm 2 Color
Display

REd

Display Color is Red

AMbR

Display Color is
Amber

GRN

Display Color is Green

ENbL

Enable

dSbL

Disable

ERRo

Error

+ OL

Input (+) Overload

+OPN

Input (+) Open

* For abbreviations of Communication Option see Communication Manual.

Отзывы: