Panel Mounting Instruction:
1.
Using the dimensions from the panel cutout diagram
shown above, cut an opening in the panel.
2.
Remove sleeve from the rear of the case by removing
thumbnuts.
3.
Insert the unit into the opening from the front of the
panel, so the gasket seals between the bezel and the
front of the panel.
4.
Slip the sleeve over the rear of the case.
5.
Tighten the thumbnuts to hold the meter firmly in the panel.
Disassembly Instruction:
If necessary, the meter may be removed from the panel and
opened.
Warning: Disconnect all ac power from the unit
before proceeding.
1.
Remove all wiring connections from the rear of the
instrument, by unplugging the power and input connectors.
2.
Remove both thumbnuts and set aside.
3.
Remove the sleeve and set aside.
4.
Remove the meter from the panel and bend the side
panel detents on the case outward to release the board.
Pull the board assembly out of the case.
WIRING
Wire the instrument according to the schematic below.
Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow all
instructions and warnings may result in injury!
This Quick Start Reference provides information
on setting up your instrument for basic operation.
The latest complete Communication and
Operational Manual as well as free Software and
ActiveX Controls are available at
www.newportUS.com/i or on the CD-ROM
enclosed with your shipment
.
SAFETY CONSIDERATION
This device is marked with the international
Caution symbol.
The Controller is a panel mount device protected in
accordance with Class II of IEC 1010. Remember that the
controller has no power-on switch. Building installation
should include a switch or circuit-breaker that must be
compliant to IEC 947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on
the top of the instrument housing.
• Always disconnect power before changing signal and
power connection.
• Do not use this instrument on a work bench without
its case for safety reasons.
• Do not operate this instrument in flammable or
explosive atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the
instrument if EMC problems persist.
MOUNTING
START HERE
Connect the main power connections in the figure shown
below.
FUSE
Connector Output Type For 115Vac For 230Vac
DC
FUSE 1
Output 1
Relay
3 A(T)
3 A(T)
-
FUSE 2
Output 2
Relay
3 A(T)
3 A(T)
-
FUSE 3
Power
N/A
100 mA(T) 100 mA(T) 100 mA(T)
FUSE 4
Power
N/A
N/A
N/A
400 mA(T)
CONFIGURATION
Button Functions in Configuration Mode
• To enter the Menu, the user must first press
a
button.
• Use this button to advance/navigate to the next
menu item. The user can navigate through all the
top level menus by pressing
a
.
• While a parameter is being modified, press this
button to escape without saving the parameter.
• Press the up
b
button to scroll through “flashing”
selections. When a numerical value is displayed
press this key to increase value of a parameter that
is currently being modified.
• Holding the
b
button down for approximately
3 seconds will speed up the rate at which the set
point value is incremented.
• In the Run Mode pressing
b
causes the display to
flash the PEAK value – press again to return to the
Run Mode.
• Press the down
c
button to go back to a previous
Top Level Menu item.
• Press this button
twice to reset the controller
to
the Run Mode.
• When a numerical value is flashing (except set point
value) press this button to scroll digits from left to
right allowing the user to select the desired digit to
modify.
• When a set point value is displayed press this button
to decrease value of a set point that is currently being
modified. Holding the
c
button down for
approximately 3 seconds will speed up the rate at
which the setpoint value is decremented.
• In the Run Mode pressing
c
causes the display to
flash the Valley value - press again to return to the
Run Mode.
• Press this button to access the submenus from a
Top Level Menu item.
• Press this button to store a submenu selection or
after entering a value — the display will flash a
STRD
message to confirm your selection.
• Press this button to reset flashing PEAK value.
• In the Run Mode, press ENTER twice to enable
Standby Mode with flashing
STBY
- press again to
return to the Run Mode.
a
d
c
b
(UP)
MENU
(DOWN)
ENTER
Reset: Except for Alarms, modifying any settings of
the menu configuration will reset the controller prior
to resuming Run Mode.
DISPLAY ABBREVIATIONS
SP1
Set Point 1 Value
SP2
Set Point 2 Value
CNFG
Configuration Menu
INPt
Input Type Menu
t.c
Thermocouple Input
k. . .J
Thermocouple Type
Rtd
RTD Input
385.2
RTD Curve and
100 _
100 _/500 _/1000 _
. . . .
Connection Type
. . . .
RTD Sensor
392.4
(2, 3, 4-Wire)
1000
PROC
Process Input
0 - 0.1
100 mV Input Voltage
0 - 1.0
1 V Input Voltage
0 - 20
20 mA Input Current
0 - 10
10 V Input Voltage
RdG
Reading Configuration
dEC
Decimal Point
F.FFF.
Decimal Point
FLtR
Filter Constant
..FFFF
Position
0001..
Filter Constant Value
IN.Rd
Input/Reading Scale
..0128
and Offset Menu
IN 1
Input 1
IN 2
Input 2
Rd 1
Reading 1
Rd 2
Reading 2
ALR1
Alarm 1 Menu
AbSo
Absolute Mode
_dEV
Deviation Mode
LtcH
Latched Mode
UNLt
Unlatched Mode
Ct.CL
Contact Closure
N.o.
Normally Open
N.c
.
Normally Closed
ActV
Active Type
AboV
Active Above
bELo
Active Below
Hi.Lo
Above High/Below
Low
bANd
Above or Below Band
A.P.oN
Alarm Enable/Disable
at Power On
ALR.L
Alarm Low Value
ALR.H
Alarm High Value
ALR.2
Alarm 2 Menu
LOOP
Loop Break Menu
b.tIM
Loop Break Time
R.AdJ
Reading Adjust
SP.dN
Set Point Deviation
OUt1
Output 1 Menu
SELF
Manual Control
ººLO
Percent Low
ººHI
Percent High
CtRL
Control Type
ON.OF
On/Off Control
4 - 20
Amplitude Control
PId
PID Control
ActN
Action Type
RVRS
Reverse Action
dRct
Direct Action
ANt1
Anti Integral
AUto
Auto PID
A.tUN
Auto Tune PID
StRt
Start Auto Tune PID
PRoP
Proportional Band
RESt
Reset Setup
RAtE
Rate Setup
CYCL
Cycle Time
dPNG
Damping Factor
dEAd
Dead Band
ANLG
Analog Output
VoLt
Voltage Output
CURR
Current Output
Out.1
Output 1
Rd 1
Reading 1
Out.2
Output 2
Rd 2
Reading 2
RAMP
Ramp Time
SOAk
Soak Time
Id
ID Code Menu
CH.Id
Change ID Code
FULL
Full ID
SP.Id
Set Point ID
COMM
Communication Option*
NONE
Communication is
Not Installed
COLR
Display Color Selection
N.CLR
Normal Color
Display
1.CLR
Alarm 1 Color Display
2.CLR
Alarm 2 Color
Display
REd
Display Color is Red
AMbR
Display Color is
Amber
GRN
Display Color is Green
ENbL
Enable
dSbL
Disable
ERRo
Error
+ OL
Input (+) Overload
+OPN
Input (+) Open
* For abbreviations of Communication Option see Communication Manual.