QT
set tachometer gain
IMM
PGM
MIP
USAGE
♦
♦
SYNTAX
xx
QT
nn or xx
QT
?
PARAMETERS
Description
xx
[ int ] -
axis number
nn
[float] -
tachometer gain
Range
xx
-
1
to
MAX AXES
nn
-
0
to
20
or
?
to read present setting
Units
xx
-
none
nn
-
Volts/Krpm
Defaults
xx
missing:
error 37, AXIS NUMBER MISSING
out of range:
error 9, AXIS NUMBER OUT OF RANGE
nn
missing:
error 38, COMMAND PARAMETER MISSING
out of range:
error xx2, PARAMETER OUT OF RANGE
DESCRIPTION
This command is used to set the DC motor tachometer gain for a Newport
Unidrive compatible programmable driver axis.
This command should be used in conjunction with
QG
(gear constant) command.
This command must to be followed by the
QD
update driver command to take
affect.
RETURNS
If the “?” sign takes the place of
nn
value, this command reports the current
setting
REL. COMMANDS
QD
-
update driver
QS -
set microstep factor
QG
-
set gear constant
QI
-
set motor maximum current
QV
-
set average motor voltage
EXAMPLE
2QT?
|
read tachometer gain setting of axis # 2
7.0
|
controller returns a
value of 7.0 V/Krpm for axis #2
2QT 6.5
|
set tachometer gain value of 6.5 V/Krpm for axis #2
2QG
0.3937
|
set gear constant to 0.3937 rev / unit for axis #2
2QD
|
update programmable driver with latest settings for axis #2
SM
|
save all controller settings to non-volatile memory
3-120
Section
3
–
Remote
Mode
Содержание ESP300 Series
Страница 1: ...ESP300 Motion Controller Driver User s Manual...
Страница 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Страница 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Страница 30: ......
Страница 230: ...4 16 Section 4 Advanced Capabilities...
Страница 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Страница 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...