FUSE PANEL

 

Technical Practice

 

FDP 1010 

10/10 GMT  

NEBS Level 3 Certified 

 

FEATURES

 

¾

  2 isolated groups (busses) of 10 GMT fuses in each (15Amps/GMT position) 

¾

  Polarity insensitive (+/-24 or +/- 48 Vdc) battery voltage 

¾

  This panel can operate at 200 Amps of output current per panel (100 Amps per Bus) 

¾

  Barrier terminal strips for fused outputs and isolated returns (grounds) 

¾

  Three sets of Form C relay contacts are provided to extend alarms 

¾

  One set of alarm contacts for each; MAJOR Bus A, MAJOR Bus B and MINOR External Input Alarm 

¾

  MINOR External Input Alarm provided on the ground signal applied to the input pin 

¾

  Cable management bar (aka. towel bar) on rear panel included  

¾

  Five spare fuse holders provided on the panel’s faceplate 

¾

  Single 1.75” mounting height (single panel space) 

¾

  Two sets of mounting brackets are supplied (1” & 1-3/4” spacing), both sets of brackets are universal for 

19” and 23” racks, with flush and offset mounting options 

¾

  NEBS level 3 certified, with zone 4 earthquake

Содержание FDP 1010

Страница 1: ...inal strips for fused outputs and isolated returns grounds Three sets of Form C relay contacts are provided to extend alarms One set of alarm contacts for each MAJOR Bus A MAJOR Bus B and MINOR External Input Alarm MINOR External Input Alarm provided on the ground signal applied to the input pin Cable management bar aka towel bar on rear panel included Five spare fuse holders provided on the panel...

Страница 2: ...pins The Normal condition of the relay exists when the panel is powered up without any blown fuses or externally activated alarms The red External Alarm LED on the units face plate will light when a ground is connected to the MINOR Alarm In terminal 20mA max signal required to activate alarm 1 6 The N250120 N L0521 Fuse Panels are made from 0 050 steel and painted black Single rack height panels a...

Страница 3: ...panel bay alarms A ground signal is supplied from another device in the bay to activate this alarm In an alarm the C contact will short to the NO contact and the NC will open Connect the alarm connections as per your alarm system requirements Newmar recommends you fuse the alarm battery supply ABS to 1A or less to protect the alarm wiring and circuitry 4 8 CHASSIS GROUND For safety reasons and as ...

Страница 4: ...kmanship and components for a period of 2 years from the date of shipment During this period any defective products shipped prepaid to Newmar will be repaired or replaced at our discretion and returned at no further cost to the customer Newmar shall not be liable for any consequential or indirect damage of any type or nature nor for any cost of reinstallation Any product that has been subject to i...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Отзывы: