IX) Specifications
Centurion Rectifiers
Input Voltage/Frequency:
90-264 VAC* / 47-63 Hz.
Input Amperage:
6 amps @ 115V and full load, 3
amps @ 230V and full load
Power Factor:
.96-.99
Output Voltage/Amperage*:
CR48-10
: -54.4 VDC, 10 amps continuous
CR24-20
: +27.2 VDC, 20 amps continuous
* 100 % output power available from 105 VAC to 264
VAC; Derate output linearly from 100% @ 105 VAC to
80 % @ 90 VAC
Line/Load
Regulation:
+/- 2 %
Ripple:
CR24-20: 1% PK-PK
CR48-10: 1% PK-PK
Protection:
Over-voltage, current limiting, over-
temperature, input and output fuses.
Fan Operation:
Continuous air flow front to rear.
Indicators/Controls:
• Output power indicators LED
• Power switch
Operating Temperature:
-10°C to +60°C; 100 % load
from 0°C to +50°C; Derate linearly to 80% load from
+50°C to +60°C and 0°C to -10°C.
Weight:
6.0 lbs.
Safety:
• EN55022 Class A
• UL 1950
• CE mark
Centurion Rectifier Shelf
Model CRS
Input:
115/230 VAC nominal
Capacity:
Up to Three Rectifiers, CR24-20 or CR48-10
Alarms/Indicators/Controls:
• Output failure contacts; Form A, Form B,
Form C, Contact rating: 1 Amp Max.
• Front panel LED indications: Minor Alarm,
Major Alarm, Output OK, Battery Over Temp
• Front panel voltage test points and adjustment
Adjustment Range: 24V: 25-29.4V, 48V: 50-59V
Battery Drain (with no AC input):
<200 mA 3 rectifiers
and controller
Mounting:
19" or 23" rack
Dimensions:
Refer to Dimensional Drawings
Weight:
10 lbs.
Safety:
UL 1950 compliant
Rectifier
A
Rectifier
B
Rectifier
C