background image

 

Newmar • PO Box 1306, Newport Beach, CA 92663                                                         

• Phone: 714-751-0488 • E-mail: [email protected] 

2.5 Rectifier 

Addressing 

Each rectifier in the system has a unique address which identifies it to the monitor.  This address is set by 
the position in the rectifier shelf and the number of the shelf.  It is read by the rectifier from the backplane 
PCB and will change if the rectifier is moved to a new location.  This address structure is set up when the 
system is built by the system manufacturer. 

2.6 

Commissioning the Rectifier 

1)  Ensure the polarity of the load and battery cables to the backplane is correct. 

2)  Plug the rectifier into the rectifier shelf using the following steps: 

 

Locate the metal tag (at the bottom/rear of the rectifier) into the chosen slot in the backplane.   

 

Engage the plastic front panel into the slot at the front of the rectifier shelf.  

 

Push the rectifier into the rectifier shelf until the connector is fully engaged. 

 

Lock the rectifier in position using the plastic retainers in the front panel. 

3)  Once the rectifier is installed into the rectifier shelf, the AC power can be turned on.  After the initial 

start up period the rectifier will be set to the desired system parameters by the monitor module via 
the serial communications. 

Содержание C2R-1000

Страница 1: ...00 854 3906 Newport Beach CA USA Centurion II Power System 24 VDC 1000 Watt 48 VDC 2000 Watt Rectifier Installation Operation Manual Model C2R 2000 Newmar 2911 W Garry Ave Santa Ana CA 92704 Tel 714 7...

Страница 2: ...1 10 Fan Cooling 3 1 11 Serial Alarm and Control Interface 3 1 11 1 Voltage Control 4 1 11 2 Rectifier Alarm states 4 1 11 3 Rectifier Shutdown 4 1 12 Post mate Connection 4 1 13 Interface Rear Conne...

Страница 3: ...ators There are 3 LED indicators on the front panel indicate the operational state of the rectifier AC This green LED indicates that mains power is connected to the unit and that the primary stages of...

Страница 4: ...the rectifier will de rate its output power to keep internal temperatures within the allowable range 1 8 Reverse Polarity Protection The rectifier has an internal reverse polarity protection fuse and...

Страница 5: ...l The AC supply is not present at the rectifier Rectifier Fail The rectifier is not functioning This could be due to high output voltage AC failure or a fault with the rectifier internally Over Temper...

Страница 6: ...Description Pin 1 2 3 Positive Output Pin 4 5 6 Negative Output Pin 7 Serial Communication Bus Pin 8 Rack Position horizontal Pin 9 Rack Position vertical Pin 10 Post mate connected to negative output...

Страница 7: ...efficiently as possible ensure the following The air at the front of the rack is at ambient temperature and not being heated by other equipment Ensure the rectifier shelf has at least 75mm 3 clear ho...

Страница 8: ...1 Ensure the polarity of the load and battery cables to the backplane is correct 2 Plug the rectifier into the rectifier shelf using the following steps Locate the metal tag at the bottom rear of the...

Страница 9: ...voltage restored Input Inrush 2x maximum input current 3 2 DC Output Software Switchable Nominal 48V 24V Rated Voltage 58V 29V Adjustable Voltage Range 43V 60V 21V 30V Maximum Rated Current 41 7A 41...

Страница 10: ...ure 20 C to 70 C Humidity 5 95 RH non condensing Altitude 2500m above sea level De rate maximum ambient temperature by 4 C per 1000m above sea level 3 4 Mechanical Dimensions W H D 111 5mm 4 39 44mm 1...

Страница 11: ...If the yellow LED is alight Check the monitor Non Urgent Alarm list 4 3 Fuses Although there are fuses inside the rectifier these are rated such that their failure indicates a fault requiring qualifi...

Страница 12: ...11 Newmar PO Box 1306 Newport Beach CA 92663 Phone 714 751 0488 E mail techservice newmarpower com 5 Ventilation Details...

Страница 13: ...ned damage by power surges or electrical storms or sustained shipping damage or repaired by any unauthorised repair centre Please contact Newmar Customer Service to obtain a Returned Materials Authori...