background image

 

New Cosmos USA, Inc. 
Natural Gas Alarm  
806NIT

 

Troubleshooting Guide  

This Gas Alarm is designed to be 
troubleshot exclusively by authorized 
professionals. 

This guide is intended for 

professional use only. 

Testing the detector

 

 

CAUTION 

If the Gas Alarm does not operate properly, 
it cannot alert the presence of natural gas. 
Take immediate action if the Gas Alarm fails 
a test.

 

Testing power

 

Press test button until you hear a “Beep” sound, then 
quickly release (within 3 seconds after pressing the test 
button). If the device is properly powered, the green LED 
will flash twice every second (for 3 seconds) to indicate that 
the power is on. 

 

 

 

 

 

 

 

 

 

Testing gas leak alarm notifications

 

Press test button until you hear a “Beep” sound, then 
continue to hold until you hear a “Beep Beep” sound 
approximately 5 seconds later. Release within 10 seconds 
of pressing the test button.

 

 

 

 

 

 

If the Gas Alarm is operating properly, the red LED will flash 
once every 2 seconds for a 12 second period, and the 
following alarm message will sound twice:  

“Beep Beep 

Beep Beep Danger 

– gas leak explosion risk – evacuate, 

then call 911.” 

 

Testing automated communications

 

Press and hold test button for at least 10 seconds, until you 
have heard a single “Beep” followed by a double beep 
(“Beep Beep”) followed by a triple beep (“Beep Beep 
Beep”).  This will enable communications test mode, and 
the green LED will flash 3 times per second for as long as 
you are in communications test mode.

 

 

 

 

 

 

Once in communications test mode, press the test button 
additional times to test whether the detector is 
communicating normally with 

your gas utility’s systems, 

able to properly transmit detector error signals, and able to 
properly transmit a low battery signal. Success will be 
indicated as follows: 

 

 

Green LED

 

Yellow LED

 

Communications test 
mode activated

 

Flashes 3x 
per second

 

Off

 

1

st

 press: normal 

communication

 

Flashes 2x 
per second

 

Off

 

2

nd

 press: proper 

transmission of device 
error signal

 

Flashes 2x 
per second

 

Flashes 3x 
per second

 

3

rd

 press: proper 

transmission of low battery 
signal

 

Flashes 2x 
per second

 

Flashes 2x 
per second

 

 

If the red LED light activates or the alarm sounds 
during any of these tests, the detector’s 
communication functions are not working properly.

 

Additional presses will cycle you back through these three 
tests for as long as you are in communications test 
mode.  Communications test mode will automatically end 
after 5 minutes.

 

Troubleshooting

 

 

Symptom

 

Cause

 

Action

 

The green LED does 
not flash even when 
the switch is pressed

 

Battery connector 
not plugged in 
completely

 

Plug in the 
battery 
connector 
completely

 

Battery is low

 

Replace the 
battery

 

The yellow LED is 
flashing.

 

Flashes twice 
every 10 seconds:

 

End of service life

 

Replace the 
detector

 

Flashes once every 
10 seconds:

 

Low battery

 

Replace the 
battery

 

 

Flashes 3 times 
every 10 seconds: 
Gas alarm trouble

 

Replace the 
detector

 

 
 

 

Содержание DeNova Detect 806NIT

Страница 1: ...or Network or power outages may prevent your gas utility from receiving or processing automated notifications from your Gas Alarm including notifications related to gas leak alarms Always follow these instructions without relying on such automated notifications This Gas Alarm will reach its end of service life in approximately 6 years from the date of installation Contact your gas utility for repl...

Страница 2: ...ully in the event that the natural gas leak alarm activates Never ignore any natural gas leak alarms EVACUATE IMMEDIATELY and take others with you Do NOT use a phone light a match or turn on or off any light switches flashlights or appliances Doing so could IGNITE a FIRE or EXPLOSION CALL 911 once you are safely outside the premises Do NOT re enter until told to do so by authorities DANGER EXPLOSI...

Страница 3: ...sehold cleaning agents ammonia based cleaners paints varnishes aerosol sprays including compressed gas dusters or any other chemical on or near this Gas Alarm Specifications Contact Details New Cosmos USA Inc 650 Warrenville Rd Suite 101 Lisle IL 60532 Tel 847 749 3064 Conforming standards UL standard UL1484 FCC Certified Detection principle MEMS hot wire semiconductor sensor Target gas Methane ga...

Страница 4: ...t mode and the green LED will flash 3 times per second for as long as you are in communications test mode Once in communications test mode press the test button additional times to test whether the detector is communicating normally with your gas utility s systems able to properly transmit detector error signals and able to properly transmit a low battery signal Success will be indicated as follow...

Страница 5: ...ent battery needed After installing battery test the Gas Alarm following instructions in Troubleshooting Guide To reinstall the included battery or install a new battery you received from your gas utility Open the battery cover on the back of the detector This cover slides out of place To open place both thumbs on the back of the battery cover where the battery cover hooks snap into place Push dow...

Отзывы: