7
5. Installation
5-1.
Installation Method
CAUTION
z
Be careful not to damage the gas detector when installing it. Otherwise, the
explosion-proof performance of the gas detector will be lost.
z
When using the Detector to prevent oxygen deficiency (anoxia) in the
surrounding air, mount the Detector at the same height as the head of the
operator.
z
Install the gas detector in places where it can be maintained and inspected with
ease.
z
Do not install the product in the following places.
- Places where the ambient temperature exceeds the operating temperature
range (0
°
C to 40
°
C).
- Places where condensation occurs.
- Places where water is directly sprayed.
- Places subject to corrosive gas.
- Places close to equipment that generates high frequencies or a magnetic field.
z
Install the gas detector in places free from vibration.
z
Install the gas detector in places free from sudden temperature changes.
z
Keep the gas detector free from impacts.
z
When installing the gas detector outdoors, be sure to install the protective cover
(optional).
z
Mount the gas detector at a height where maintenance inspection can be
performed easily and considering the fact that oxygen deficiency (anoxia)
occurs easily at a height of 75 to 150 cm from the floor.