-Materials used in areas designated as non-combustible must be rated as non-combustible per NFPA 220 
Standard on Types of Building Construction, or reported as passing ASTM E 136, Standard Test Method for 
Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C. 
WARNING: common finishing materials not approved for use: 

-

 

Paper-faced gypsum board (drywall) including Type X Fire Rated board is not a non-combustible 
material. 

-

 

WonderBoard brand boards are commonly used as a backerboard for tile. WonderBoard backerboard 

is not a non-combustible material. 

-

 

Durock brand cement board contains a polymer coated fiberglass mesh. This can smell when heated. 
For this reason Durock cement board is not approved. 

-Non-combustible finishing materials shown in yellow must be insulated from any combustible elements of 
the construction such as wood framing. This can be accomplished by one of the following: 
Option 1: Construct the enclosure using only non-combustible finishing materials and framing. 

Use steel studs and non-combustible material to build the enclosure for the burner. 
Option 2: Create an air gap behind the non-combustible finishing material by following the method shown 

below. The gap between the material can be left open or insulated with mineral wool. 

Method for creating an air gap behind non-combustible finishing material. 

Hardibacker 500 or other non-combustible rated cement board is recommended for use in constructing the 
enclosure. Do not use Durock or WonderBoard brand cement board. These boards are not rated as non-
combustible materials and will off gas or deteriorate when subjected to heat. 
1. Install a ½” thick cement board to the wood framing. 
2. Cut 2” wide strips of ½” thick cement board to use as spacers between the first layer of ½” thick 

cement board and a second layer of ½” thick cement board. This will create an air gap between the two 
boards. 

3. Install a second layer of cement board to the strips. The gaps between the strips can be left open or 

insulated with mineral wool. 

4. Install the desired non-combustible finishing material to the second layer of cement board. 

 

- The bottom of the enclosure that holds the burner and other areas not shown in yellow can be 
constructed from any construction material including combustible materials. 
- In the non-combustible area shown in yellow use only fasteners and adhesives that are resistant to a 

temperature of 300°F (150°C). For an adhesive, High Temp 450°F silicone adhesive is recommended. 
-The minimum F dimension of 14” allows for a 2” tall junction box. If a taller junction box is used increase 

the depth of the cavity. 

 

 

Содержание AA-11-04745

Страница 1: ...e installing or operating the NetZero FLA Burner NetZero FLA Burner Series Models AA 11 04745 NZ40B AA 11 04746 NZ48B AA 11 04747 NZ60B AA 11 04748 NZ72B AA 11 04749 NZ90B AA 11 04750 NZ108B WARNING I...

Страница 2: ...ptional Equipment 5 3 CLEARANCES AND INSTALLATION 6 3 1 Burner Clearances and Cavity Measurements 6 3 2 Burner Clearances and Cavity Measurements for Multiple Burners 8 3 3 Placing the Burner 9 3 4 In...

Страница 3: ...emperatures keep children clothing and furniture away 4 Risk of indoor air pollution use unvented decorative appliance only in well ventilated areas People with breathing problems should consult a phy...

Страница 4: ...e appliance rating at maximum burner adjustment See Table A for recommended minimum room size If the burner is installed in a room smaller than the recommended minimum room size or in a home of unusua...

Страница 5: ...NZ90B 1 1 1 4 2 4 2 NZ108B 1 1 1 6 2 6 2 2 2 Optional Equipment Applies to see through peninsula and island installations For information on installing the large glass barrier kits reference the large...

Страница 6: ...2B 58 72 NZ90B 115V 60 Hz min 20A 77 90 NZ108B 97 108 Ensure that burner flame is positioned a minimum of 40 inches away from curtains flammable materials and other sources of ignition Be aware of dra...

Страница 7: ...between the material can be left open or insulated with mineral wool Method for creating an air gap behind non combustible finishing material Hardibacker 500 or other non combustible rated cement boa...

Страница 8: ...be calculated from the total length of the burners placed together An example is given below Measurements Burner Model L in A in B in C in D in E in F in G in H in NZ40B 31 1 8 10 1 4 16 Total Length...

Страница 9: ...click to watch the video instruction https www youtube com watch v b5dETFNTBW4 feature youtu be 3 4 Installing Technical Glass Scan or click to watch the video instruction https www youtube com watch...

Страница 10: ...Installations Installation Requiring Large Glass Barrier Kit See Through Peninsula and Island Installations For these installations the Large Glass Barrier Kit must be used For additional information...

Страница 11: ...gle Sided Left Corner Right Corner and Three Sided Installations See Through and Peninsula Installations If an air conditioning vent or fan is located near the burner the vent or fan must be positione...

Страница 12: ...the tank is empty the message NO FUEL is displayed Open the fuel inlet I and firmly connect the pump hose A click and power cable B II the message REFUELLING PLEASE WAIT is displayed c Place the fuel...

Страница 13: ...OP for 3 seconds Choose ON OFF to enable disable the function Set time Set the hour by pressing next press and set minutes Accept with Remote Control Programming a new remote or connecting one remote...

Страница 14: ...i Fi CONFIG in the menu Time to finish the configuration is 5 minutes c Enable the Wi Fi connection on your mobile device and connect to planika123 network if the network is not visible on the list di...

Страница 15: ...Turn the burner OFF wait for a min 5 minutes and turn the burner ON ERROR 02 03 04 10 16 31 32 41 51 61 Contact the Service Department 6 MAINTENANCE NetZero burners are considered maintenance free me...

Отзывы: