7. Strip 1/4 inch of insulation from three wires at the remote

sensor. Install the wires in the terminals using the table

below.

Cat5/Cat5e cable color code:

RS+V = Green with White Stripe

RS2 = Brown with White Stripe

RS1 = Green

Shielded cable color code:

RS+V = Color 1 in pair

RS2 = Drain wire

RS1 = Color 2 in pair

A

NOTE:

the wire color going to each terminal. The order

of the wires on the thermostat are not the same as the

sensor.

8. Connect the wires

on the thermostat

backplate to the

terminals labeled

RS1, RS2 and RS+V.

Make sure each

terminal on the

sensor is wired to

the terminal with

the same name on

the thermostat.

9. Set the DIP Switches on the bottom right of the sensor to

the appropriate sensor type.

10.Set the jumper to match the total number of sensors

directly connected to the thermostat; 1-2, 3-5, or 6+

sensors.

C

WARNING:

Do Not Count The Additional NT-URS

Sensors Used For Indoor Averaging.

OFF

ON

# Sensors

1-2

3-5

6+

UP

UP

Sensor Counting Example 1:

You are connecting an

INDOOR

sensor,

OUTDOOR

sensor,

AUX1,

and

AUX2

. The sensor count is 4 and the correct

jumper configuration is the middle jumper 3-5.

Sensor Counting Example 2:

You are connecting 6

INDOOR

sensors (Averaged) and one

INDOOR HUMIDITY

sensor. The sensor count is 2 and the

correct jumper configuration it the top jumper 1-2.

Sensor Counting Example 3:

You are connecting 3

INDOOR

sensors (Averaged),

OUTDOOR

Sensor,

AUX1, AUX2, AUX3,

and a

INDOOR

HUMIDITY

Sensor. The sensor count it 6 and the correct

jumper configuration is the bottom jumper 6+.

11.Reattach the thermostat faceplate to the backplate. (See

your thermostat installation manual for instructions.)

For X-Series thermostats, the

remote sensor will display in

the upper left of the display.

Tap on the upper left of the

display to cycle through the

different connected sensors.

The names of the sensors

will display in the dot matrix

area of the display.

For UP32 and US32

thermostats, press the two

buttons on the right side of

the thermostat to activate

the secondary display for

remote sensors. Press the Up

or Down buttons to cycle

through the sensor types.

Rotate through indoor,

outdoor, humidity, and AUX

on the display. There will be

a value next to the icon for

the sensor type that has

been selected.

12.If there are no additional sensors to be added to the sensor

network, close the sensor case by hooking in the top, then

snapping it on the bottom.

USING NT-URS AS HUMIDITY SENSOR

Install the NT-URS sensor using the single sensor instructions.

The NT- URS can be configured as a dedicated humidity only

sensor. Reference the switch position in the diagram to the right.

You can view the humidity value in the thermostat’s web server

and on the thermostat faceplate, as described in

Step 11.

ADDING EXTERNAL SENSOR PROBES

Add the NT-RS-S or NT-FS to the NT-URS by connecting two

wires from the probe to the terminals designated 1 and 2 on the

NT-URS. (Connection to NT-RS-S shown below)

The wires can be connected with either polarity. Use 2-

conductor cable (22AWG minimum) with a maximum length of

300 feet (or 90m).

C

IMPORTANT:

If the NT-URS is initially configured with an

external probe and the probe fails or is disconnected, the NT-

URS will stop to reporting and the Diagnostic LED will

continually light until the problem is corrected.

NT-RS-S connected to NT-URS Sensor

(Optional NT-FS connection not shown)

Available Sensor Probes

from Network Thermostat

NT-URS AS AUX1, AUX2, OR AUX3 SENSOR

The NT-URS can report as as AUX1, AUX 2 or AUX3 sensor. In

this configuration, you can use either the internal temperature

sensor or an external probe.
When the NT-URS is initially detected by the thermostat, it will

check first from the external probe connections, if no probe is

detected, the sensor will default to the internal temperature

sensor.

C

IMPORTANT:

If the NT-URS is initially configured with an

external probe and the probe fails or is disconnected, the NT-

URS will stop to reporting and the Diagnostic LED will

continually light until the problem is corrected.

Page 2

SENSOR TYPE CONFIGURATION

INDOOR

Uses Internal

temperature sensor or

Indoor probe like the

NT-FS or NT-FS-S

OUTDOOR

Uses outdoor probe.

Has specific curve.Probe

connects to 2-screwless

terminals Ignores Temp/

Hum Sensor

INDOOR HUMIDITY

ONLY

Uses Internal Humidity

sensor.

AUX 1

Uses internal temperature

sensor or external probe.

The external probe

connects to 2-screwless

terminals

AUX 3

Uses internal temperature

sensor or external probe.

The external probe

connects to 2-screwless

terminals

AUX 2

Uses internal temperature

sensor or external probe.

The external probe

connects to 2-screwless

terminals

1-2

3-5

6+

NUMBER OF SENSOR
CONFIGURATION

NT-RS-S

Surface Mount

10K Temp Sensor

NT-OUTDOOR

Weatherized

10K Temp Sensor

NT-PROBE-SS8

8” 10K Temp Sensor

(Inquire about other types)

NT-FS

Flush Mount

10K Temp Sensor

UP

UP

NT-URS

Set as Humidity Only Sensor

AUX 1

Uses internal temperature

sensor or external probe.

The external probe

connects to 2-screwless

terminals

AUX 3

Uses internal temperature

sensor or external probe.

The external probe

connects to 2-screwless

terminals

AUX 2

Uses internal temperature

sensor or external probe.

The external probe

connects to 2-screwless

terminals

NetX Thermostat

OFF

ON

# Sensors

1-2

3-5

6+

UP

UP

NT-URS

NT-RS-S

NetX Thermostat

OFF

ON

# Sensors

1-2

3-5

6+

UP

UP

NT-URS

To AUX

PROBE