50
Calculating the length of DC wires
Example 2:
This example uses the following given values.
AWG
Strand
DC resistance(1) [
Ω
/ft.]
Total cable length(2)
[ft]
25
°
C
75
°
C
25
°
C
75
°
C
12
Solid
.0017
.0020
75
64
12
7/20
.0015
.0018
85
71
12
19/25
.0017
.0020
75
64
12
65/30
.0018
.0022
71
58
12
165/34
.0016
.0019
80
67
1
. Data from Alpha Wire, wire manufacturer
2.
Combined positive and negative run
Total cable length
=
Total cable length
=
= 75 ft
R
CABLE
DC resis.
1
.128Ω
.0017Ω/ft
Given
V
DROP
= 2V
Maximum voltage drop through input source
and
cable
V
MIN
= 40V
Minimum input voltage
I
MAX
= 8.6V
Maximum input current at 40V
R
SOURCE
≅
0