background image

 

 

Example#3 

based on MinTime = 15 Minutes, MaxTime= 1 Hour,

 

PowerChange=2W

 

 

                           

                                    

MaxTime

 

 

 

 

 

MinTime       

  

     MinTime        MinTime

  

       MinTime       MinTime          MinTime 

 

 

0H

          15

th

 M         

30

th

 M

         45

th

 M         1H         1H15

th

M        

1H30

th

M

                     

          

 

 

 

  Remarks:   

1.

 

Compare the collected data with the last reported data. If the amount of data change is greater than ReportableChange, the 

device will report based on the MinTime interval. If the data change is not greater than the last reported data, the device will 

report based on the MaxTime interval.   

2.

 

For the energy consumption detection device, because the device is a constant power supply device, it is not recommended to 

set the MinTime interval value too high in order to obtain the status information in real time. It is recommended to use the 

default 2 seconds. If users need to control frequent report recommendations to adjust ReportableChange and MaxTime.   

3.

 

After the device sends a packet (regardless of whether the data has changed, such as pressing a button or the maximum time 

is due), another MinTime / MaxTime calculation cycle is initiated.   

6. Product Installation

 

This product does not have a waterproof function. After the screening is completed, please place it indoors. 

 

Note: 

The energy data of R816B is saved once every 10 seconds if the memory chip is AT24C02, once every 10 seconds for AT2402. 

After power off, the data within 10 seconds will be gone.   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Collects data 

13W 

REPORT ON 

 

Collects data   

9W 

Does not report 

 

 

Collects data 

10W 

REPORTS   

 

 

Collects data 

12W 

Does not report 

 

 

Collects data 

14W 

Does not report 

 

 

Collects data 

13W 

Does not report 

 

 

Collects data 

14W 

REPORT 

 

 

Power Change   

over 2W 

Содержание R816B

Страница 1: ...Monitoring US type R816B User Manual Copyright Netvox Technology Co Ltd This document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written permission of NETVOX Technology The specifications are subject to change without prior notice ...

Страница 2: ...2 2 Appearance 3 3 Main Characteristic 3 4 Operation 4 5 Data Report 5 5 1 Example of ReportDataCmd 6 5 2 Example of ConfigureCmd 7 5 3 Example for MinTime MaxTime logic 8 6 Product Installation 9 7 Important Maintenance Instruction 10 ...

Страница 3: ...wireless technology LoRa is a wireless communication technology dedicated to long distance low power consumption Its spread spectrum modulation method greatly increases the communication distance compared with other communication methods and can be widely used in long distance low rate IoT wireless communication fields in various occasions Such as automatic meter reading building automation equipm...

Страница 4: ...er supply Simple operation and setting Compatible with LoRaWANTM Class C Frequency hopping spread spectrum Applicable to third party platforms Actility ThingPark TTN MyDevices Cayenne Over current alarm Automatically disconnect the load due to over current Switch Indicator Network Indicator Switch Button Socket 1 Socket 2 Factory Restoring Key inside ...

Страница 5: ...device verification information on the gateway or consult your platform server provider Function Key Press and hold the factory restoring key for 5 seconds Restore to factory setting The network indicator flashes for 10 times success The network indicator remains off fail Press and hold the factory restoring key for 10 seconds The network indicator flashes once when the button is pressed for 5s an...

Страница 6: ... done Default setting MaxTime 0x0384 900s MinTime 0x0002 2s Mintime is recommended to set by default 2 seconds Need to control to reduce frequent Report recommendations by adjusting reportchange and Max Interval Current Change 0x0064 100mA Power Change 0x0014 20W Note 1 The device reports the ON OFF status energy over current alarm first and after 10 seconds reports the voltage current and power 2...

Страница 7: ...LoadData 0x01 0x73 0x01 OnOff 1Byte OFF_0x00 ON_0x01 Energy 4Bytes unit 1wh OverCurrentAlarm 1Byte 0 noalarm 1 alarm 1 DashCurrentAlarm 1Byte 0 noalarm 1 alarm 2 PowerOffAlarm 1Byte 0 noalarm 1 alarm 0x02 Vol 2Bytes Unit 1V Current 2Bytes Unit 1mA Power 2Bytes Unit 1W Reserved 2Bytes fixed 0x00 1 R816B does not support Dash Current Alarm 2 R816B does not support Power Off Alarm First uplink report...

Страница 8: ...d 0x00 Read CurrentStatus 0x94 Reserved 9Bytes Fixed 0x00 Config ReportReq 0x01 MinTime 2bytes Unit s MaxTime 2bytes Unit s CurrentChange 2byte Unit 1mA PowerChange 2byte Unit 1W Reserved 1Byte Fixed 0x00 Config ReportRsp 0x81 Status 0x00_success Reserved 8Bytes Fixed 0x00 ReadConfig ReportReq 0x02 Reserved 9Bytes Fixed 0x00 ReadConfig ReportRsp 0x82 MinTime 2bytes Unit s MaxTime 2bytes Unit s Cur...

Страница 9: ...3 Example for MinTime MaxTime logic Example 1 based on MinTime 1 Hour MaxTime 1 Hour PowerChange 2W MaxTime MaxTime MinTime MinTime 0H 1H 2H Note MaxTime MinTime Data will only be report according to MaxTime MinTime duration regardless PowerChange value Example 2 based on MinTime 15 Minutes MaxTime 1 Hour PowerChange 2W MaxTime MinTime MinTime MinTime MinTime 0H 15th M 30th M 45th M 1H 2H Collects...

Страница 10: ...al time It is recommended to use the default 2 seconds If users need to control frequent report recommendations to adjust ReportableChange and MaxTime 3 After the device sends a packet regardless of whether the data has changed such as pressing a button or the maximum time is due another MinTime MaxTime calculation cycle is initiated 6 Product Installation This product does not have a waterproof f...

Страница 11: ...melt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device Rough handling of equipment can destroy internal circuit boards and delicate structures Do not clean the device with strong chemicals detergents or strong detergents Do no...

Отзывы: