5
5. Data Report
The device will immediately send a version package report and a report data with leak detection status and voltage value.
The device sends data in the default configuration before any configuration is done.
Maximum time: Max Interval
Minimum time: Min Interval (by default, the current voltage value and the leak detection status value are detected every Min
Interval)
Default reportchange: batteryvoltagechange ---- 0x01(0.1V)
Note:
The actual data sending cycle will be programmed before shipment.
The interval between two reports must be the minimum time
R718WB default Max Interval = 60min, Min Interval = 60min
(if there is special custom shipment, the setting is changed according to customer requirements)
While the water leak detection is triggered:
The leak detected a change in state and immediately issued a report. No leaks status: 0, leak status: 1.
The data report can be decoded by the Netvox LoraWAN Application Command document
and http://www.netvox.com.cn:8888/page/index
Data report configuration and sending period are as following:
Report Configuration
ConfigReportReq
R718W
B
0x01
0x47
MinTime(2b
ytes Unit:s)
MaxTime(2by
tes Unit:s)
BatteryChange(1by
te Unit:0.1v)
Reserved (4Bytes,Fixed
0x00)
ConfigReportRsp
0x81
Status(0x00_
success)
Reserved (8Bytes,Fixed 0x00)
ReadConfigReportReq
0x02
Reserved (9Bytes,Fixed 0x00)
ReadConfigReportRsp
0x82
MinTime(2b
ytes Unit:s)
MaxTime(2by
tes Unit:s)
BatteryChange(1by
te Unit:0.1v)
Reserved (4Bytes,Fixed
0x00)
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable Change
Current
Change≥
Reportable Change
Current
Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval